TROUBLESHOOTING
1-127August 9, 2005
D SERIES CONTROLLER
TROUBLESHOOTING AND COMPONENT REPLACEMENT
Kaaaw sk
ERROR CODE E4521 ABMA-PDP) Status OFFLINE. XX
An error occurred in the ABMA-PDP module, and the status of AnyBus PROFIBUS-DP
master changed to OFFLINE.
Use the sub-sub-code XX as a troubleshooting aid, clear the cause of the error and
reset the error.
If the error recurs, cycle the controller power OFF and ON.
_____________________________________________________________________
ERROR CODE E4522 ABMA-PDP) I/O data communication error. XX
During I/O communication, configuration data is downloaded to the interface card, then
communication is disconnected.
Use the sub-code XX as a troubleshooting aid, clear the cause of the error and reset
the error.
_____________________________________________________________________
ERROR CODE E4523 ABMA-PDP) sending of timed out I/O data. XX
The ABMA-PDP module is overloaded and output signals from the AS system cannot
be processed within the allowed time.
Check the fieldbus cable connections and repair as necessary.
Use the sub-code XX as a troubleshooting aid, clear the cause of the error and reset
the error.
_____________________________________________________________________
ERROR CODE E4524 ABMA-PDP) Timeout of receiving I/O data. XX
ABMA-PDP module overload, input signals from the slave cannot be processed within
the allowed time.
Check the fieldbus cable and connections, repair/replace as necessary
.
Use the sub-code XX as a troubleshooting aid, clear the cause of the error and reset
the error.
_____________________________________________________________________