Lennox International Inc 090V60C, 070V36B, 090V36C, 110V60C installation instructions 2 51mm

Models: 090V60C 110V60C 090V36C 070V36B DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

1 64
Download 64 pages 9.7 Kb
Page 18
Image 18
2" (51mm)

Details of Intake and Exhaust Piping Terminations for Direct Vent Installations

NOTE − In Direct Vent installations, combustion air is tak- en from outdoors and flue gases are discharged to out- doors.

NOTE − Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used and the flue gasses may impinge on the building ma- terial, a corrosion−resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the optional tee is used, the protective shield is recommended. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an appropriate sealant. See figure 21.

Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 19 through 28 show typical termina- tions.

1 − Exhaust and intake exits must be in same pressure zone. Do not exit one through the roof and one on the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.

2 − Intake and exhaust pipes should be placed as close together as possible at termination end (refer to il- lustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall termina- tions.

3 − On roof terminations, the intake piping should termi- nate straight down using two 90° elbows (See figure 19).

4 − Exhaust piping must terminate straight out or up as shown. A reducer may be required on the exhaust pip- ing at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 9.

NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe.

FIELD−SUPPLIED WALL TERMINATION OR (15F74) WALL RING TERMINATION KIT

NOTE − FIELD−PROVIDED

 

 

REDUCER MAY BE

 

1/2" (13mm) ARMAFLEX

REQUIRED TO ADAPT

 

 

INSULATION IN

LARGER VENT PIPE SIZE

 

 

UNCONDITIONED SPACE

TO TERMINATION.

 

 

 

 

 

 

SIZE TERMINATION

 

 

 

PER TABLE 9

 

 

 

D

 

 

 

B

 

C

 

STRAIGHT

 

A

APPPLICATION

 

 

 

1/2" (13mm) ARMAFLEX INSULATION

 

IN UNCONDITIONED SPACE

 

E

 

D

* WALL

 

 

 

 

 

SUPPORT

 

 

 

 

 

 

B

 

 

 

A

 

C

 

EXTENDED

 

 

 

APPLICATION

See venting table 7 for maximum venting lengths with this arrangement.

*Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust).

2" (51mm)

3" (76mm)

Vent Pipe

Vent Pipe

Inches(mm)

3"(76mm) MAX.

SIZE TERMINATION PIPE PER TABLE 9.

UNCONDITIONED

A−Minimum clearance

 

 

above grade or average

12" (508MM)

12" (508MM)

snow accumulation

 

 

 

 

 

B−Maximum horizontal

 

 

8" (203mm) MIN

12" (305mm) ABOVE

AVERAGE SNOW

ACCUMULATION

ATTIC SPACE

1/2" (13mm) FOAM

INSULATION IN UNCONDITIONED SPACE

separation between

6" (152MM)

6" (152MM)

intake and exhaust

 

 

 

 

 

C−Minimum from

8" (203MM)

8" (203MM)

end of exhaust to

 

 

inlet of intake

 

 

D−Maximum exhaust

12" (305MM)

20" (508MM)

pipe length

 

 

3" (76mm) OR

2" (51mm) PVC

PROVIDE SUPPORT

FOR INTAKE AND

EXHAUST LINES

DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 19

E−Maximum wall support

 

 

distance from top of each

6" (152MM)

6" (152MM)

pipe (intake/exhaust)

 

 

FIGURE 20

Page 18

Page 18
Image 18
Lennox International Inc 090V60C, 070V36B, 090V36C, 110V60C installation instructions 2 51mm