Lennox International Inc 090V36C, 070V36B, 110V60C, 090V60C Configuring Unit Size Code

Models: 090V60C 110V60C 090V36C 070V36B DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

1 64
Download 64 pages 9.7 Kb
Page 56
Image 56
Configuring Unit Size Code

Configuring Unit Size Code

Power−Up − Number displayed represents by integrated control unit size code (furnace model and capacity). If three horizontal bars are displayed followed by continuous E203, furnace control does not recognize unit size code. Configure per the following:

Manual backgroundManual background

 

 

Furnace control in IDLE mode

 

 

 

 

 

 

No

Yes

 

No heating, cooling or indoor fan

 

 

 

 

operation)

 

 

To enter

Field

Test

 

Mode: push and hold

 

button

next

to

_

7−segment LED display

 

until solid dash symbol

 

appears.

Release

 

button.

 

 

 

If alarm

is

present,

 

furnace

control will

_

display

error

code.

If

 

alarm is not present solid

 

dash

starts blinking on

 

7−segment LED display.

 

Push and hold button until the solid

P

 

symbol is displayed on the 7−segment

P

LED. Release button. This mode allows

the user to select a unit size code number

 

that matches the furnace model size and

 

capacity.

 

 

 

 

 

IMPORTANT: Field replacement controls may need to be manually configured to validate furnace unit size code.

Solid P starts

blinking on P 7−Segment LED

Push and hold button. Integrated control will display unit size code number for each furnace model for five seconds.

Turn room thermostat to OFF

UNIT SIZE

 

CODE

FURNACE MODEL

H

SLP98DFV−070−36B

J

SLP98DFV−090−36C

L

SLP98DFV−090−48C

n

SLP98DFV−090−60C

o

SLP98DFV−110−60C

 

 

When the correct unit size code is displayed, release button. Selected code will flash for 10−second period. During that period, hold push button until code stops blinking (disappear for 2 seconds). Integrated control will store code in memory and will automatically exit Field Test Mode and reset. (If second period expires or push button is held less than five seconds, control will automatically exit Field Test Mode and go into IDLE mode without storing unit size code. If this happens, programming function must be repeated).

 

 

 

 

 

 

 

 

Verify that the selected unit size code is correct

 

and stored in non−volatile memory by cycling

 

 

 

 

the 24 volt power to the furnace control. (At 24

 

 

volt power−up of the furnace control, the

 

 

7−segment LED will display a unit size code. If

 

 

three horizontal bars display, board does not

 

 

recognize unit size code. Programming

 

 

function must be repeated)

 

 

FINISHED

Page 56

Page 56
Image 56
Lennox International Inc 090V36C, 070V36B, 110V60C, 090V60C installation instructions Configuring Unit Size Code