Lennox International Inc 090V60C, 070V36B, 090V36C, 110V60C installation instructions

Models: 090V60C 110V60C 090V36C 070V36B DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

1 64
Download 64 pages 9.7 Kb
Page 28
Image 28

1 − The power supply wiring must meet Class I restric- tions. Protected by either a fuse or circuit breaker, se- lect circuit protection and wire size according to unit nameplate.

NOTE − Unit nameplate states maximum current draw. See table for maximum over−current protection.

TABLE 11

SLP98DF Model

Maximum Over−Current

Protection (Amps)

 

 

 

07036B, 09036C, 09048C

15

 

 

09060C, 11060C

20

 

 

2 − Holes are on both sides of the furnace cabinet to facili- tate wiring.

3 − Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing.

4 − Before connecting the thermostat or the power wiring, check to make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to check the length of the wire.

5 − Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wir- ing diagram shown in figure 40 and table 14. Use 18−gauge wire or larger that is suitable for Class II ra- ting for thermostat connections.

NOTE − Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the SLP98DFV integrated control unless this is a communicating thermostat installation with a non− communicating outdoor unit.

6 − Electrically ground the unit according to local codes or, in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the field make−up box.

7 − One line voltage 1/4" spade terminal is provided on the furnace integrated control. Any electronic air cleaner rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con- nected to one of the provided neutral terminals. See figure 44 for location of terminal. This terminal is ener- gized when the indoor blower is operating.

8 − One line voltage ade terminal is provided

on the furnace integrated control. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 44 for loca- tion of terminal. This terminal is energized in the heat- ing mode when the indoor blower is is operating.

9 − One 24V

grated control terminal block. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit being connected to either ground or the 4 for location of

terminal.

10 −Install the room thermostat according to the instruc- tions provided with the thermostat. See table 14 for thermostat connections. If the furnace is being matched with a heat pump, refer to the instruction packaged with the dual fuel thermostat.

NOTE − The discharge air temperature sensor is intended to be mounted downstream of the heat exchanger and air

conditioning coil. It must be placed in free airflow, where

other accessories (humidifiers, UV lights etc.) will not inter- fere with its accuracy. Wiring distance between the furnace and discharge air sensor should not exceed 10 ft. when

wired with 18−gauge thermostat wire.

TABLE 12

Run Length

Wire Run Length

AWG #

Insulation/Core Types

 

 

 

Less than 100’ (30m)

18

Color−coded, temperature

rating 95ºF (35ºC) mini-

 

 

More than 100’ (30m)

16

mum, solid core. (Class II

Rated Wiring)

 

 

 

 

 

TABLE 13

Run Length

Wire Run Length

AWG #

Insulation/Core Types

 

 

 

Maximum length of wiring

 

Color−coded, temperature

for all connections on the

18

rating 95ºF (35ºC) mini-

RSBus is limited to 1500

mum, solid core. (Class II

 

feet (457 meters).

 

Rated Wiring)

 

 

 

Thermostat Selection

The SLP98DFV is designed to operate in a variable rate ca- pacity mode using a two−stage thermostat. The SLP98DFV will automatically adjust firing rate based upon thermostat cycle times.

The icomfort Toucht thermostat must be used in commu- nicating applications. Refer to the instructions provided with the thermostat for installation, set−up and operation.

For optimal performance in non−communicating applica- tions, Lennox recommends use of a ComfortSense® 7000 high quality electronic digital thermostat or any other with adjustable settings for 1st stage / 2nd stage on / off differen- tials and adjustable stage timers.

Lennox recommends the following two−stage thermostat set−up for optimal variable rate capacity mode:

First heat stage differential set to 1/2 to 1 degree F; second heat stage differential set to 1/2 or 1 degree F; second heat stage upstage timer disabled, or set to maximum (1 hr mini- mum).

Indoor Blower Speeds

NOTE − When the SLP98DFV is used with icomfort Toucht thermostat, proper indoor blower speed selec- tions are made by the communicating thermostat.