Lennox International Inc DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

Models: 090V60C 110V60C 090V36C 070V36B DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

1 64
Download 64 pages 9.7 Kb
Page 39
Image 39

Switches 14 through 19 −− Heating Mode Blower Speed

−−These switches are factory set at the OFF position which provides 100 % of normal speed during HIGH HEAT de- mand, 70% of normal speed during MID−RANGE HEAT demand and 35% of normal speed during LOW HEAT de- mand. Switches 14, 15 and 16 are used to adjust the LOW HEAT blower motor speed. Switches 17, 18 and 19 are used to adjust the HIGH HEAT blower motor speed. Table 21 provides the heating mode blower speeds that will result from different switch settings. Refer to tables beginning on page 37 for corresponding cfm values.

TABLE 21

Low Heat Blower Speeds

 

Blower

DIP SWITCH SETTINGS

Thermostat

Speed

 

 

 

Demand

Adjust-

14

15

16

 

ments

 

 

 

 

 

+15%

On

Off

On

Low Heat

+7.5%

On

Off

Off

Normal

Off

Off

Off

(R to W1)

−7.5%

On

On

Off

 

 

−15%

On

On

On

 

TABLE 22

 

 

 

High Heat Blower Speeds

 

 

 

 

 

 

 

Blower

DIP SWITCH SETTINGS

Thermostat

Speed

 

 

 

Demand

Adjust-

17

18

19

 

ments

 

 

 

 

 

+15%

On

Off

On

High Heat

+7.5%

On

Off

Off

(R to

Normal

Off

Off

Off

W1 & W2)

−7.5%

On

On

Off

 

 

−15%

On

On

On

On−Board Links

On−Board links must be clipped (when applicable) before unit is placed into operation with a non−communicating thermostat.

On−Board Link W914 (DS to R) −− Figure 44

On−board link W914 is a clippable connection between ter- minals DS and R on the integrated control. W914 must be cut when the furnace is installed with either the Harmony IIIt zone control or a thermostat which features humidity control. If the link is left intact the PMW signal from the Har- mony III control will be blocked and also lead to control damage. Refer to table 24 for operation sequence in ap- plications including SLP98DFV, a thermostat which fea- tures humidity control and a single−speed outdoor unit. Table 25 gives the operation sequence in applications with a two−speed outdoor unit.

On−Board Link W951 (R to O) −− Figure 44

On−board link W951 is a clippable connection between ter- minals R and O on the integrated control. W951 must be cut when the furnace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the link is left intact, terminal will remain ener- gized eliminating the HEAT MODE in the heat pump.

On−Board Link W915 (Y1 to Y2) −− Figure 44

On−board link W915 is a clippable connection between ter- minals Y1 and Y2 on the integrated control. W915 must be cut if two−stage cooling will be used. If the link is not cut the outdoor unit will operate in second−stage cooling only.

Diagnostic LED −− Figure 44

The seven−segment diagnostic LED displays operating status, target airflow, error codes and other information. The table on Page 53 lists diagnostic LED codes.

Diagnostic Push Button −− Figure 44

The diagnostic push button is located adjacent to the seven−segment diagnostic LED. This button is used to en- able the Error Code Recall mode and the Field Test mode. Press the button and hold it to cycle through a menu of op- tions. Every five seconds a new menu item will be dis- played. When the button is released, the displayed item will be selected. Once all items in the menu have been dis- played, the menu resumes from the beginning until the but- ton is released.

Error Code Recall Mode

Select "E" from the menu to access the most recent ten er- ror codes. Select Error Code Recall menu to

clear all error codes. Button must be pressed a second time while

Press the button until a solid " is displayed to exit the Error Code Recall mode.

Field Test Mode

Use the diagnostic push button to scroll through the menu as described above. Release the button when the LED flashes est mode.

While in the Field Test mode the technician can:

DInitiate furnace ignition and move to and hold low−fire rate by applying a R to W1 jumper.

DInitiate furnace ignition sequence and move to and hold high−fire rate by applying a jumper from R to W1 and W2.

DInitiate furnace ignition sequence and move to and hold mid−fire rate by applying a jumper to R and W2.

DApply then remove the jumper from R to W1 and W2 to change the firing rate from low fire to mid fire and high fire.

DA vent calibration sequence can be initiated even if a thermostat signal is not present. Press and hold the push button until a solid

button and calibration will begin. The furnace will per- form the high−fire and low−fire pressure switch calibra- tions and display ter calibration, the LED will

return to the flashing .

During Field Test mode operation, all safety switches are still in the circuit (they are not by−passed) and indoor blower performance and timings will match DIP switch selections. Current furnace firing rate, indoor blower CFM and flame signal will be displayed. To exit the Field Test mode, press and hold the button. The menu will resume from the begin- ning. Also, cycle the main power to exit the Field Test mode. The integrated control will automatically exit the Field Test mode after 45 minutes of operation.

Page 39

Page 39
Image 39
Lennox International Inc DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE, 070V36B On−Board Links