Lennox International Inc 090V60C, 070V36B, 090V36C Table Non−Combustible Floor Opening Size

Models: 090V60C 110V60C 090V36C 070V36B DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

1 64
Download 64 pages 9.7 Kb
Page 8
Image 8
TABLE 1

TABLE 1

NON−COMBUSTIBLE FLOOR OPENING SIZE

 

Front to Rear

Side to Side

Cabinet Width

 

 

 

 

in.

mm

in.

mm

 

 

 

 

 

 

B Cabinet (17.5")

19 − 3/4

502

16 − 5/8

422

 

 

 

 

 

C Cabinet (21")

19 − 3/4

502

20−1/8

511

 

 

 

 

 

NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.

SLP98DF UNIT

SLP98DF UNIT

PROPERLY SIZED FLOOR OPENING

SUPPLY AIR

PLENUM

COMBUSTIBLE FLOORING BASE

PROPERLY

 

SIZED FLOOR

SUPPLY AIR

OPENING

PLENUM

FIGURE 8

Installation on Combustible Flooring (Figure 9)

1 − When unit is installed on a combustible floor, a down- flow combustible flooring base must be installed be- tween the furnace and the floor. The base must be or- dered separately. See table 2 for opening size to cut in floor.

Manual background CAUTION

The furnace and combustible flooring base shall not be installed directly on carpeting, tile, or other com- bustible material other than wood flooring.

TABLE 2

COMBUSTIBLE FLOORING BASE OPENING SIZE

Cabinet

Catalog

Front to Rear

Side to Side

 

 

 

 

Width

Number

in.

mm

in.

mm

 

 

 

 

 

 

 

 

B Cabinet

11M60

22

559

18 − 3/4

476

(17.5")

 

 

 

 

 

 

 

 

 

 

 

C Cabinet

11M61

22

559

22 − 3/4

578

(21")

 

 

 

 

 

 

 

 

 

 

 

FIGURE 9

2 − After opening is cut, set combustible flooring base into opening.

3 − Check fiberglass strips on combustible flooring base to make sure they are properly glued and positioned.

4 − Lower supply air plenum into combustible flooring base until plenum flanges seal against fiberglass strips.

NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.

5 − Set the furnace over the plenum.

6 − Ensure that the seal between the furnace and plenum is adequate.

Installation on Cooling Coil Cabinet (Figure 10)

NOTE − Downflow combustible flooring base is not used.

1 − Refer to reverse−flow coil installation instructions for correctly sized opening in floor and installation of cabi- net.

2 − When cooling cabinet is in place, set and secure the furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.

3 − Seal the cabinet and check for air leaks.

Page 8

Page 8
Image 8
Lennox International Inc 090V60C, 070V36B, 090V36C, 110V60C installation instructions Table Non−Combustible Floor Opening Size