Lennox International Inc 090V60C, 070V36B, 090V36C, 110V60C Condensate Piping

Models: 090V60C 110V60C 090V36C 070V36B DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

1 64
Download 64 pages 9.7 Kb
Page 23
Image 23
Condensate Piping

Condensate Piping

This unit is designed for either right- or left-side exit of con- densate piping. Refer to figure 32 for condensate trap loca- tions.

NOTE − If necessary the condensate trap may be installed up to 5 feet away from the furnace. Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.

NOTE − Vinyl tubing may be used for condensate drain. Tubing must be 1−1/4" OD X 1" ID and should be attached to the drain on the trap using a hose clamp.

CONDENSATE TRAP AND PLUG LOCATION (shown with left side exit of condensation)

1−1/2 in. Manual background

3 − Install drain trap using appropriate PVC fittings, glue all joints. Glue the provided drain trap as shown in fig- ure 34. Route the condensate line to an open drain.

4 − If unit will be started immediately upon completion of installation, prime trap per procedure outlined in Unit Start−Up section.

Condensate line must be sloped downward away from condensate trap to drain. If drain level is above con- densate trap, condensate pump must be used. Con- densate drain line should be routed within the condi- tioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heating cable kit is available from Lennox in various lengths; 6 ft. (1.8m) − kit no. 26K68; 24 ft. (7.3m) − kit no. 26K69; and 50 ft. (15.2m) − kit no. 26K70.

CAUTION

Do not use copper tubing or existing copper condensate lines for drain line.

CONDENSATE TRAP LOCATION

(shown with right side exit of condensation)

Trap

Plug

(same other right side)

(same on left side)

FIGURE 32

1 − Determine which side condensate piping will exit the unit, location of trap, field−provided fittings and length of PVC pipe required to reach available drain.

2 − Remove plug (figure 32) from the cold end header box

Trap Can Be Installed a

Maximum Of 5’ From Furnace

(PVC Only)

1" min.

*5’ max.

to drain

Field−Provided Vent

min. 1" Above

Condensate Drain

at the appropriate location on the side of the unit. Install 1/2 NPT male field provided fitting into cold end head- er box. Do Not Over Tighten. Use teflon tape or ap- propriate pipe dope.

*Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.

FIGURE 33

Page 23

Page 23
Image 23
Lennox International Inc 090V60C, 070V36B, 090V36C, 110V60C installation instructions Condensate Piping