Lennox International Inc DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

Models: 090V60C 110V60C 090V36C 070V36B DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

1 64
Download 64 pages 9.7 Kb
Page 19
Image 19
Manual background

B

D

C

2 A

 

B

 

 

 

 

 

 

D

 

Intake

 

C

3

 

 

 

 

 

 

 

 

1

 

 

 

 

 

A

 

Front View of

 

 

Intake and Exhaust

 

 

 

 

 

Exhaust

 

 

 

 

 

Intake

Exhaust

 

 

 

TABLE 8

 

D

 

 

2" (51mm)

3" (76mm)

 

 

 

 

1

 

Vent Pipe

Vent Pipe

E

A− Clearance above

 

 

 

 

 

 

 

grade or average snow

12" (508MM) Min.

12" (508MM) Min.

B

 

accumulation

 

 

 

B−Horizontal

 

 

 

 

6" (152MM) Min.

6" (152MM) Min.

 

 

separation between

 

 

24" (610 MM) Max

24" (610 MM) Max

 

 

intake and exhaust

 

12"

 

 

 

C−Minimum from

 

 

 

 

 

 

C

 

end of exhaust to

9" (227MM) Min.

9" (227MM) Min.

 

inlet of intake

2

 

 

 

 

 

 

 

A

 

D−Exhaust pipe length

12" (305MM) Min.

12" (305MM) Min.

 

16" (405 MM) Max. 20" (508MM) Max.

 

 

 

 

 

E−Wall support distance

 

 

 

 

from top of each pipe

6" (152MM) Max.

6" (152MM) Max.

 

 

(intake/exhaust)

 

 

 

 

NOTE − See unit installation instructions for proper exhaust pipe termination size reduction.

1The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do

not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.

2 As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommende- d. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.

3Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away from adjacent property. The exhaust must never be directed toward the combustion air inlet.

FIGURE 21

Page 19

Page 19
Image 19
Lennox International Inc DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE, 070V36B, 090V36C, 110V60C