Page 55
Image 55
Indoor blower motor temperature is too high.

Integrated Control Diagnostic Codes (continued)

Code

Diagnostic Codes/Status of Equipment

Action Required to Clear and Recover

E 295

Indoor blower motor temperature is too high.

Indoor blower motor over temperature (motor tripped on internal protector), Check motor bear- ings, amperes. Replace if necessary.

E 310

Discharge error sensor failure − No error if disconnected. Only shown if

Discharge air temperature(DATS) out of range,

 

shorted or out−of−range.

code is activated during "Field test mode".

 

 

 

E 311

Heat rate reduced to match indoor blower air flow. Replace filter or repair

Furnace blower in cutback mode due to restricted

 

duct restriction.

airflow. Check filter and ductwork. To clear replace

 

 

filter if needed or repair/ add ductwork.

 

 

 

E 312

Restricted air flow in cooling or continuous fan mode is lower than cfm setting.

Restricted airflow − Indoor blower is running at a reduced cubic feet per minute (Cutback Mode) − The variable speed motor has pre−set speed and torque limiters to protect the motor from damage caused by operating out of its designed parameters (0 to 0.8 inches water column total external static pressure). Check filter and ductwork. To clear re- place filter if needed or repair/ add ductwork.

E 313

Indoor or outdoor unit capacity mismatch.

Incorrect Indoor /outdoor capacity code selected. Check for proper configuration in installation instruc- tions. Alarm is just a warning. The system operation is not impacted at all and alarm would clear when Commissioning is exited.

E 331

Global network connection − Communication link problem.

For Future Use.

 

 

 

E 347

No 24 Volt output on Y1 to C with non−communicating outdoor unit.

Y1 relay / Stage 1 failed (Pilot relay contacts did not

 

 

close or the relay coil did not energize).

 

 

 

E 348

No 24 Volt output on Y2 to C with non−communicating outdoor unit.

Y2 relay / Stage 2 failed (Pilot relay contacts did not

 

 

close or the relay coil did not energize).

 

 

 

E 349

No 24 Volts between R & O with non−communicating outdoor unit (Dual

Configuration link R to O needs to be cut on control

 

fuel module required for heat pump application).

board.

 

 

 

E 401

LSOM − Compressor ran more than 18 hours in air conditioning mode.

Compressor protector is open. Check for high head

 

 

pressure, check compressor supply voltage. Out-

 

 

door unit power disconnect is open , compressor

 

 

circuit breaker or fuse(s) is open, broken wire or

 

 

connector is not making contact. Low or high pres-

 

 

sure switch open if present in the system. Compres-

 

 

sor contactor has failed to close.

 

 

 

E 402

LSOM − Outdoor unit system pressure trip.

Compressor ran over 18 hours in air conditioning

 

 

mode.

 

 

 

E 403

LSOM − Compressor short−cycling (Running less than 4 minutes).

Outdoor unit pressure trip. Check dirty coil, fan mo-

 

 

tor, refrigerant charge.

 

 

 

E 404

LSOM − Compressor rotor locked.

Compressor short cycling (Running less than 4 min-

 

 

utes).

 

 

 

E 405

LSOM − Compressor open circuit.

Check capacitor, wiring, hard start kit , replace com-

 

 

pressor.

 

 

 

E 406

LSOM − Compressor open start circuit.

Check compressor for hot (cool down) , check pres-

 

 

sures, fan motor etc. Replace compressor if unable

E 407

LSOM − Compressor open run circuit.

to get circuit to close and compressor to operate.

 

 

E 408

LSOM − Compressor contactor is welded.

 

 

 

 

E 409

LSOM − Compressor low voltage.

Replace contactor.

 

 

 