Lennox International Inc 110V60C, 070V36B, 090V36C rigid leg will not touch the blower housing

Models: 090V60C 110V60C 090V36C 070V36B DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE

1 64
Download 64 pages 9.7 Kb
Page 7
Image 7
rigid leg will not touch the blower housing.

NOTE − The 1/2 hp blower motor used in some SLP98DFV unit is equipped with three flexible legs and one rigid leg.

The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet

used with a flexible mounting leg). The bolt and washer

must be removed before the furnace is placed into op-

eration. After the bolt and washer have been removed, the

rigid leg will not touch the blower housing.

SLP98DF070V36B and

SL98DF090V036C WITH 1/2 HP

BLOWER MOTOR

RIGID LEG

remove shipping bolt and washer

FIGURE 6

Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al- cove installations are shown in figure 7.

Manual background WARNING

Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.

Manual background WARNING

Improper installation of the furnace can result in per- sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace.

In platform installations with furnace return, the fur- nace should be sealed airtight to the return air ple- num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al- low absolutely no sagging, cracks, gaps, etc.

For no reason should return and supply air duct sys- tems ever be connected to or from other heating de- vices such as a fireplace or stove, etc. Fire, explo- sion, carbon monoxide poisoning, personal injury and/or property damage could result.

The unit may be installed three ways in downflow applica- tions: on non−combustible flooring, on combustible flooring using a base, or on a reverse−flow cooling coil cabinet. Do not drag the unit across the floor in the downflow posi- tion. Floor and flange damage will result.

Refer to figure 7 for clearances in downflow applica- tions.

Downflow Application Installation Clearances

 

Top

Left Side

Right Side

 

Bottom

 

 

Top

 

0

 

 

 

*Front

 

0

 

 

 

Back

 

0

 

 

 

Sides

 

0†

 

 

 

Vent

 

0

 

 

 

Floor

 

NC‡

 

 

 

*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Allow proper clearances to accommodate condensate trap and vent pipe installation.

‡The furnace may be installed on a combustible wood floor if an op- tional base is installed between the furnace and the combustible floor.

FIGURE 7

Installation on Non−Combustible Flooring (Figure 8)

1 − Cut floor opening keeping in mind clearances listed on unit rating plate. Also keep in mind gas supply connec- tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.

2 − Flange warm air plenum and lower the plenum into the opening.

3 − Set the unit over the plenum and seal the plenum to the unit.

4 − Ensure that the seal is adequate.

Page 7

Page 7
Image 7
Lennox International Inc 110V60C, 070V36B, 090V36C, 090V60C rigid leg will not touch the blower housing