(335 MM)

 

 

 

(335 MM)

 

 

 

 

 

SEE NOTE (7)

 

 

 

 

 

 

13.2"

 

 

 

 

 

13.2"

 

 

BACK WALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FOR SPACING

REAR FLOOR

 

 

BRACKET

 

 

SEE NOTE (2)

 

 

FOR SPACING

 

 

REAR CABINET

 

(832 MM)

BASE BRACKET

BACK

 

WALL

32.75"

 

APPROX 1/2"

 

 

FRONT DOOR

OF CABINET

HARDWARE

SUPPLIED

FRONT CABINET

BASE BRACKET

Figure 11 Seismic anchor

WALL

FRONT

 

 

 

FLOOR LINE

REAR FLOOR

 

 

BRACKET

SIDE

 

 

FLOOR ANCHOR

 

 

HARDWARE

 

 

 

FRONT FLOOR

 

(146 MM)

(NOT SUPPLIED)

 

 

BRACKET

(256 MM)

5.75"

FIGURE 2

(107 MM)

(107 MM)

4.2"

10.1"

4.2"

 

FLOOR ANCHOR

HARDWARE

NOT SUPPLIED

FLOOR LINE

FRONT FLOOR

BRACKET

FIGURE 3

drawing: 100 – 250 amp

24

TOP VIEW

SYSTEM SEISMIC ANCHORING, FIGURE 1

NOTES:

1.RECOMMENDED FLOOR ANCHOR: 1/2" ITW RAMSET/RED HEAD SELF DRILLING ANCHOR, ICBO #ER-1372 OR EQUIVALENT (NOT (SUPPLIED). FOLLOW MANUFACTURER'S INSTRUCTIONS.

2.POSITION REAR FLOOR BRACKETS ON FLOOR AT LEAST .75" FROM BACK WALL. MARK LOCATION AND DRILL HOLES (FIG. 1) TO A MINIMUM DEPTH OF 4.12" INTO THE CONCRETE.

3.INSTALL REAR CABINET BASE BRACKET (FIG. 2) TO EXISTING HOLES ON UNDERSIDE OF UNIT WITH TABS FACING BACK WALL. USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

NOTE, LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER BRACKET IS SECURED.

4.INSTALL FRONT CABINET BASE BRACKET (FIG. 3) TO EXISTING HOLES ON UNDERSIDE OF UNIT WITH BENT FLANGE FACING FRONT. USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

NOTE, LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER BRACKET IS SECURED.

5.MOVE CABINET INTO POSITION WITH REAR TABS INTO SLOTS OF FLOOR BRACKET. TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR BRACKET (FIG. 2). THEN ATTACH FRONT FLOOR BRACKETS TO FRONT CABINET BASE BRACKET BUT DO NOT FULLY TIGHTEN HARDWARE.

6.MARK HOLE LOCATIONS AND REMOVE BRACKETS. DRILL AND INSTALL FLOOR BRACKETS. UNIT DOOR CAN BE REMOVED FOR BETTER ACCESS. REINSTALL FRONT FLOOR BRACKETS TO FRONT CABINET BRACKETS WITH SUPPLIED HARDWARE AND TORQUE TO 235 LB-IN (26.5 Nm), (FIG. 3).

7.IF SIDE WALLS ARE PRESENT, 5.0 INCH MINIMUM DISTANCE FROM EITHER SIDE WALL IS REQUIRED.

8.REAR AND FRONT FLOOR BRACKETS, AND REAR AND FRONT CABINET BASE BRACKETS ARE 1010 STEEL AND APPROX. .25 INCH THICK.

PS211105

Rev. 0

Liebert STS2

Installation Drawings

Page 32
Image 32
Liebert 100-1000A user manual Seismic anchor, Liebert STS2