Options

6.7LED Display

A light-emitting diode display is available to replace the standard liquid crystal display touch screen control. The display provides monitoring and control throuh a series of LEDs and buttons. LEDs alert you when a problem occurs. A PC running terminal emulation software connected to the RS-232 port is needed to access the data and configuration settings.

6.8Remote Source Selection

The Remote Source Selection allows the preferred input source to be chosen from a remote location. A user supplied normally open dry contact allows the user to remotely select a source to be the preferred source in the same process as the local source transfer selection.

The unit’s preferred source selection and Remote Source Selection are active at the same time, with the Liebert STS2 following the last request for a preferred source change, regardless of whether it was from the local or Remote Source Selection controls.

See 10.3 - Enabling Remote Source Selection for instructions on enabling the Remote Source Selection.

See Figures 21 and 22 for the location of the Remote Source Selection option.

See 5.5 - Remote Source Selection Wiring on page 13 and Figure 23 for information on the control wiring.

6.9Key Lockout Switch

The key lockout switch activates a software lockout of the touch screen display to prevent manual transfers and configuration changes. When locked out, the touch screen becomes a read only display. A key is needed to do manual transfers or change settings.

The alarm silence button is not disabled when in the lockout position.

The switch is located behind the front door but can be operated without opening the front door. See Figures 8 to 10 for the key lockout location on each unit.

See 14.1.4 - Key Lockout Switch for instructions on using the key lockout switch.

6.10Redundant Output Breaker

An output plug-in, non-automatic circuit breaker is provided which allows redundancy in the output power path. The breaker is connected in parallel with the output plug-in non-automatic circuit breaker.

6.11Transfer Inhibit

Transfer Inhibit prevents the Liebert STS2 from transferring under certain conditions. When a customer-supplied closed dry contact is provided, the Liebert STS2 will not transfer and remain on its present source even if the source is no longer supplying power.

This option requires an Input Contact Isolator board (see 6.4 - Input Contact Isolator Board).