29

 

 

NOTES:

 

 

1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).

 

 

2. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH

 

 

REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT

 

 

CONDUIT SIZE, AND REPLACE.

.51 DIA.

PEM NUT

3. CONTROL WIRING AND POWER WIRING MUST BE RUN

GROUND BUS

INPUT/OUTPUT BUS

IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE

RUN IN A SEPARATE CONDUIT FROM INPUT CABLES.

FRONT VIEW

RIGHT SIDE VIEW

4. ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE

 

 

NOT RECOMMENDED.

 

 

5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL

 

PEM NUT

AND LOCAL ELECTRICAL CODES.

 

 

 

6. HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT,

 

 

 

 

NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT

 

 

 

NEUTRAL BUS

INCLUDES 1/2" BOLTS, WASHERS, AND NUTS FOR

 

 

 

CONNECTING CABLES TO THE BUS BARS.

 

 

SOURCE 1 INPUT

RIGHT SIDE VIEW

7. THE TORQUE REQUIREMENT FOR 1/2"-13 PEM NUTS IS

 

Ø A, Ø B, Ø C

 

428 INCH-LBS. (48 N-m).

 

 

 

 

SOURCE 1 INPUT Ø A

 

 

 

 

 

SOURCE 1 INPUT Ø B

 

 

 

 

SOURCE 2 INPUT

SOURCE 1 INPUT Ø C

 

 

 

 

Ø A, Ø B, Ø C

 

 

 

 

 

 

 

 

 

CB1

CB2

NEUTRAL BUS

 

 

 

 

 

 

 

 

 

 

 

 

SOURCE 1

 

SOURCE 2

 

 

 

CB1

 

CB2

 

CB4

 

 

 

 

 

 

 

CB5

 

 

 

 

 

 

 

 

K1

 

K2

 

NEUTRAL

 

K2 K3

CB4

CB3

K1 K3

CB5

BUS

SYSTEM OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

Ø A, Ø B, Ø C

 

 

 

 

 

 

CB3

 

 

 

 

 

 

FRONT

 

 

SYSTEM OUTPUT

 

 

 

 

 

 

 

 

 

GROUND

SECTION A-A

ONE-LINE DIAGRAM

 

 

 

BUS

 

 

 

 

SIDE VIEW

 

FRONT VIEW

 

 

 

PS212400

 

 

 

Rev. 2

(WITH FRONT PANELS REMOVED)

 

 

 

 

 

Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breaker

Installation Drawings

Page 37
Image 37
Liebert 100-1000A user manual Section A-A ONE-LINE Diagram