29
|
| NOTES: |
|
| 1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS). |
|
| 2. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH |
|
| REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT |
|
| CONDUIT SIZE, AND REPLACE. |
.51 DIA. | PEM NUT | 3. CONTROL WIRING AND POWER WIRING MUST BE RUN |
GROUND BUS | INPUT/OUTPUT BUS | IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE |
RUN IN A SEPARATE CONDUIT FROM INPUT CABLES. | ||
FRONT VIEW | RIGHT SIDE VIEW | 4. ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE |
|
| NOT RECOMMENDED. |
|
| 5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL |
| PEM NUT | AND LOCAL ELECTRICAL CODES. |
|
|
| 6. HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT, |
| ||
|
|
| NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT |
| ||
|
| NEUTRAL BUS | INCLUDES 1/2" BOLTS, WASHERS, AND NUTS FOR |
| ||
|
| CONNECTING CABLES TO THE BUS BARS. |
| |||
| SOURCE 1 INPUT | RIGHT SIDE VIEW | 7. THE TORQUE REQUIREMENT FOR | |||
| Ø A, Ø B, Ø C |
| 428 |
|
| |
|
| SOURCE 1 INPUT Ø A |
|
|
| |
|
| SOURCE 1 INPUT Ø B |
|
|
| |
| SOURCE 2 INPUT | SOURCE 1 INPUT Ø C |
|
|
| |
| Ø A, Ø B, Ø C |
|
|
| ||
|
|
|
|
|
| |
CB1 | CB2 | NEUTRAL BUS |
|
|
|
|
|
|
|
|
|
| |
|
| SOURCE 1 |
| SOURCE 2 | ||
|
|
| CB1 |
| CB2 |
|
CB4 |
|
|
|
|
|
|
| CB5 |
|
|
|
|
|
|
|
| K1 |
| K2 |
|
NEUTRAL |
| K2 K3 | CB4 | CB3 | K1 K3 | CB5 |
BUS | SYSTEM OUTPUT |
|
|
|
|
|
|
|
|
|
|
| |
| Ø A, Ø B, Ø C |
|
|
|
|
|
| CB3 |
|
|
|
|
|
| FRONT |
|
| SYSTEM OUTPUT |
|
|
|
|
|
|
|
| |
| GROUND | SECTION |
|
|
| |
| BUS |
|
|
|
|
SIDE VIEW
| FRONT VIEW |
|
|
| PS212400 |
|
|
| Rev. 2 | ||
(WITH FRONT PANELS REMOVED) |
|
| |||
|
|
|
Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breaker
Installation Drawings