See Note 2
| + - |
|
|
| No customer |
|
| connection |
No customer |
|
|
connection |
|
|
40 | 1 2 3 |
|
|
| |
TB1 | TB2 | TB3 TB3 |
|
| J3 |
|
|
Notes:
1.Wire size and type: 10/100
2.Maximum cable length 1000 feet (300 meters) with twisted pair cable #22 AWG minimum. Signal voltage 5VDC, current 10mA.
3.Refer to the Liebert Intellislot Web/485 Card’s installation, operation & maintenance manual for configuration details.
4.All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit.
5.Refer to control connection location diagram of static transfer switch for location of Liebert Intellislot Web/485 card option.
6.All wiring must be in accordance with national and local electrical codes.
Ethernet Network |
|
See Notes 1 and 2 | Interconnection Cable |
PS213008
Rev. 02
Figure 27 Control wiring for the Liebert IntelliSlot SNMP/Web/Modbus 485 card
Installation Drawings