Customer-supplied interconnection cable to Modbus

See Note 2

 

+ -

 

 

 

No customer

 

 

connection

No customer

 

 

connection

 

 

40

1 2 3

 

 

 

TB1

TB2

TB3 TB3

 

DB-9

J3

 

 

RS-232 (DB-9 connector) for setup only. Uses standard computer serial port cable

Notes:

1.Wire size and type: 10/100 base-T ethernet cable with RJ-45 plug connector. The length is limited by internet standards.

2.Maximum cable length 1000 feet (300 meters) with twisted pair cable #22 AWG minimum. Signal voltage 5VDC, current 10mA.

3.Refer to the Liebert Intellislot Web/485 Card’s installation, operation & maintenance manual for configuration details.

4.All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit.

5.Refer to control connection location diagram of static transfer switch for location of Liebert Intellislot Web/485 card option.

6.All wiring must be in accordance with national and local electrical codes.

Ethernet Network

 

RF-45 Connector

Customer-Supplied

See Notes 1 and 2

Interconnection Cable

PS213008

Rev. 02

Figure 27 Control wiring for the Liebert IntelliSlot SNMP/Web/Modbus 485 card

Installation Drawings

Page 48
Image 48