Installation Drawings
38

Figure 25 Control wiring for the input contact isolator board option

21534 67 1411981012131516

“NO CUSTOMER CONNECTION”

INPUT CONTACT ISOLATOR BOARD02-810012-XX

J51

PS213002

Rev. 03

NOTES:
1. Customer control wiring connection points are Terminals 1 through 16
(see Table J51).
2. Customer-provided, normally open, dry contacts for user alarm messages.
3. Refer to installation, operation and maintenance manual for configuring the
Input Contact Isolator board option.
4. All control wiring (by others) must be run separate from power wiring. Control
wiring runs should not be combined in the same conduit.
5. Refer to static transfer switch control connection diagram (Figure 21 or 22) for
location of Input Contact Isolator board option.
6. Signal voltage: 100mA @ 12VDC.
7. Maximum cable length 500 ft. (152 m) with #16 AWG flexible, stranded cable.
8. All wiring must be in accordance with national and local electrical codes.
9. When the Transfer Inhibit option is supplied, connect a N.O. dry contact
(customer-supplied) to Input Contact 8 (Pins 15 and 16). When the customer
contact closes, transfers will be inhibited as long as the contact remains closed.
Input Contact 8 is factory-set so no setup is required. The Transfer Inhibit option
prevents Input Contact 8 from being used for any other input.

Table J51

Input
Contact Pin No.
11
2
23
4
35
6
47
8
59
10
611
12
713
14
815
16