SEE NOTE (7) FOR SPACING
(832 MM) 32.75"
WALL
(335 MM) | (335 MM) |
|
13.2" | 13.2" | BACK WALL |
|
| REAR FLOOR |
|
| BRACKET |
|
| SEE NOTE (2) |
|
| FOR SPACING |
FRONT
REAR CABINET |
| FRONT DOOR |
BASE BRACKET | BACK | OF CABINET |
| WALL | HARDWARE |
|
| |
| APPROX 1/2" | SUPPLIED |
|
| FLOOR ANCHOR |
FLOOR LINE | REAR FLOOR | HARDWARE |
NOT SUPPLIED | ||
| BRACKET |
|
FRONT CABINET |
BASE BRACKET |
Figure 12 Seismic anchor drawing: 400
SIDE
FLOOR ANCHOR | FLOOR LINE |
HARDWARE | FRONT FLOOR |
–
25
FRONT FLOOR BRACKET
(107 MM) 4.2"
(462 MM) 18.2"
TOP VIEW
(146 MM)
5.75"
(107 MM) 4.2"
(NOT SUPPLIED) | BRACKET | ||
FIGURE 2 |
| FIGURE 3 | |
|
|
|
|
600 amp Liebert
SYSTEM SEISMIC ANCHORING, FIGURE 1
NOTES:
1.RECOMMENDED FLOOR ANCHOR: 1/2" ITW RAMSET/RED HEAD SELF DRILLING ANCHOR, ICBO
2.POSITION REAR FLOOR BRACKETS ON FLOOR AT LEAST .75" FROM BACK WALL. MARK LOCATION AND DRILL HOLES (FIG. 1) TO A MINIMUM DEPTH OF 4.12" INTO THE CONCRETE.
3.INSTALL REAR CABINET BASE BRACKET (FIG. 2) TO EXISTING HOLES ON UNDERSIDE OF UNIT WITH TABS FACING BACK WALL. USE SUPPLIED HARDWARE AND TORQUE TO 365
NOTE, LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER BRACKET IS SECURED.
4.INSTALL FRONT CABINET BASE BRACKET (FIG. 3) TO EXISTING HOLES ON UNDERSIDE OF UNIT WITH BENT FLANGE FACING FRONT. USE SUPPLIED HARDWARE AND TORQUE TO 365
NOTE, LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER BRACKET IS SECURED.
5.MOVE CABINET INTO POSITION WITH REAR TABS INTO SLOTS OF FLOOR BRACKET. TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR BRACKET (FIG. 2). THEN ATTACH FRONT FLOOR BRACKETS TO FRONT CABINET BASE BRACKET BUT DO NOT FULLY TIGHTEN HARDWARE.
6.MARK HOLE LOCATIONS AND REMOVE BRACKETS. DRILL AND INSTALL FLOOR BRACKETS. UNIT DOOR CAN BE REMOVED FOR BETTER ACCESS. REINSTALL FRONT FLOOR BRACKETS TO FRONT CABINET BRACKETS WITH SUPPLIED HARDWARE AND TORQUE TO 235
7.IF SIDE WALLS ARE PRESENT, 5.0 INCH MINIMUM DISTANCE FROM EITHER SIDE WALL IS REQUIRED.
8.REAR AND FRONT FLOOR BRACKETS, AND REAR AND FRONT CABINET BASE BRACKETS ARE 1010 STEEL AND APPROX. .25 INCH THICK.
PS211405
Rev. 0
STS2
Installation Drawings