.51 DIA. | PEM NUT |
GROUND BUS | INPUT/OUTPUT BUS |
FRONT VIEW | RIGHT SIDE VIEW |
PEM NUT
NOTES:
1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).
2.TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT CONDUIT SIZE, AND REPLACE.
3.CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE
RUN IN A SEPARATE CONDUIT FROM INPUT CABLES.
4. ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE NOT RECOMMENDED.
Figure 14 Electrical field
| NEUTRAL BUS |
| 5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL |
RIGHT SIDE VIEW |
| AND LOCAL ELECTRICAL CODES. |
SOURCE 1 INPUT Ø A, Ø B, Ø C
6.HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT, NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT INCLUDES 1/2" BOLTS, WASHERS, AND NUTS FOR CONNECTING CABLES TO THE BUS BARS.
7.THE TORQUE REQUIREMENT FOR
428
27
CB1
CB4
NEUTRAL
BUS
SOURCE 2 INPUT Ø A, Ø B, Ø C
CB2
CB5
CB3
SYSTEM OUTPUT Ø A, Ø B, Ø C
FRONT
SOURCE 1 INPUT Ø A
SOURCE 1 INPUT Ø B
SOURCE 1 INPUT Ø C
NEUTRAL BUS
SOURCE 1
| CB1 |
|
| K1 |
|
K2 K3 | CB4 | CB3 |
SOURCE 2
CB2
K2
K1 K3 CB5
connections drawing: 100 – 250 amp Liebert STS2 with single
GROUND
BUS
SECTION
SYSTEM OUTPUT
ONE-LINE DIAGRAM
output
Installation
FRONT VIEW | SIDE VIEW |
(WITH FRONT PANELS REMOVED) |
|
PS212100
Rev. 3
breaker
Drawings