PEM NUT
GROUND BUS | .51 DIA. | INPUT/OUTPUT BUS | |
FRONT VIEW | RIGHT SIDE VIEW | ||
|
SOURCE 1 INPUT
SOURCE 2 INPUT
.51 DIA.
NOTES:
1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS). |
2. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH |
REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT |
CONDUIT SIZE, AND REPLACE. |
3. CONTROL WIRING AND POWER WIRING MUST BE RUN |
IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE |
RUN IN A SEPARATE CONDUIT FROM INPUT CABLES. |
4. ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE |
NOT RECOMMENDED. |
5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL |
AND LOCAL ELECTRICAL CODES. |
6. HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT, |
NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT |
INCLUDES 1/2" BOLTS, WASHERS, AND NUTS FOR |
CONNECTING CABLES TO THE BUS BARS. |
Figure 18 Electrical field connections
CB1 |
Ø A, Ø B, Ø C |
NEUTRAL BUS
7. THE TORQUE REQUIREMENT FOR |
31
CB4 |
CB2 |
CB5
GROUND
BUS
SYSTEM OUTPUT
ØA, Ø B, Ø C
CB3
RIGHT SIDE VIEW
428 INCH-LBS. (48 N-m).
SOURCE 1
INPUT Ø A
SOURCE 1
INPUT Ø B
SOURCE 1
INPUT Ø C
NEUTRAL
BUS
SOURCE 1
| CB1 |
|
| K1 |
|
K2 K3 | CB4 | CB3 |
SOURCE 2
CB2
K2
K1 K3 CB5
drawing: 800 – 1000 amp Liebert STS2 with
NEUTRAL |
BUS |
FRONT |
SECTION
SYSTEM OUTPUT
single output
Installation
FRONT VIEW
(WITH FRONT PANELS REMOVED)
SIDE VIEW
PS212800 Rev. 2
breaker
Drawings