Installation Drawings

Figure 23 Control wiring for remote source selection option

See Note 1

Source 1

Source 2

Preferred

Preferred

S1 GND

S2 GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

TB50

Remote Source Selection

NOTES

1.Customer-provided normally open dry contacts. Rating 10mA at 30VDC.

2.Maximum cable length 500 ft. (152m) with #16 AWG, 300V minimum flexible stranded cable.

3.All control wiring (by others) must be run separate from power wiring . Control wiring runs should not be combined in the same conduit.

4.Refer to Static Transfer Switch control diagram for location of remote source selection opt.

5.All wiring must be in accordance with national and local electrical codes.

PS213007

Rev. 02