TECHNICAL SPECIFICATIONS - V300-I (K1363-8, K1363-9)
Height Width Depth Weight
18.7 in. 10.8 in. 22.2 in. 64 lbs.
475 mm 274 mm 564 mm 29 Kg

PHYSICAL DIMENSIONS

THREE PHASE SINGLE PHASE
Standard Input Current Code
Voltage at Rated Output Number
200/230/280-415/440 43/39/25- 9826, 9827,
50/60 25/22 10036, 10037,
10132, 10133
Volts at
Rated
Duty Cycle Amps Amperes
60% Duty Cycle 300 32
100% Duty Cycle 250 30
Welding Constant Open Auxiliary
Current Range Circuit Voltage Power
5-300 Amps 60-70 VDC 42 VAC, 5.5 Amps
24 VAC, 1 Amp
*115 VAC, 2 Amps
*Not on all codes
Standard Input Current Code
Voltage at Rated Output Number
200/230/380-415/440 53/47/32- 9826, 9827,
50/60 32/29 10036, 10037,
10132, 10133
Volts at
Rated
Duty Cycle Amps Amperes
60% Duty Cycle 200 28
100% Duty Cycle 165 26.5
Welding Constant Open Auxiliary
Current Range Circuit Voltage Power
5-200 Amps 60-70 VDC 42 VAC, 5.5 Amps
24 VAC, 1 Amp
*115 VAC, 2 Amps
*Not on all codes

INPUT

RECOMMENDED INPUT WIRE AND FUSE SIZES

Type 75°C
Type 75°C Copper
Fuse Input Copper Ground
(Superlag) Ampere Wire in Wire in
Input or Rating Conduit Conduit
Voltage Breaker on AWG (IEC) AWG (IEC)
Frequency(1) Size Nameplate Sizes Sizes
200/50-60 60 43 6 (16mm2)10 (6mm2)
220/50-60 60 39 8 (10mm2)10 (6mm2)
380/50-60 35 25 10 (6mm2)10 (6mm2)
415/50-60 35 25 10 (6mm2)10 (6mm2)
440/50-60 35 22 10 (6mm2)10 (6mm2)
Type 75°C
Type 75°C Copper
Fuse Input Copper Ground
(Superlag) Ampere Wire in Wire in
Input or Rating Conduit Conduit
Voltage Breaker on AWG (IEC) AWG (IEC)
Frequency(1) Size Nameplate Sizes Sizes
200/50-60 80 53 6 (16mm2)10 (6mm2)
220/50-60 70 47 6 (16mm2)10 (6mm2)
380/50-60 50 32 8 (10mm2)10 (6mm2)
415/50-60 50 32 8 (10mm2)10 (6mm2)
440/50-60 50 29 10 (6mm2)10 (6mm2)