REPORT CONSOLE TROUBLE

The factory setting does not report Console trouble events to the Central Station.

Alternately, the communicator can be programmed to report Console trouble events. These include all conditions that light the Console’s BATTERIES or TROUBLE indicator. It also includes low Console backup battery.

PROGRAMMING STEP #108

PROGRAM

0 FOR NO CONSOLE TROUBLE

1 FOR CONSOLE TROUBLE

STORE PROGRAM

REPORT FORCE ARMINGThe factory setting does not send force arming reports.

Alternately, the communicator can be programmed to report force arming anytime the Console is armed with one or more bypassed sensors.

The factory set reporting code for force arming is “65” (Code 574 with Ademco).

NOTE: If force arming is enabled, and the Console is force armed (armed with an open sensor) remotely by telephone, or with the RA-2400 Remote Access software, the caller will be disconnected if the communicator is enabled.

PROGRAMMING STEP #110

PROGRAM

0 FOR NO FORCE ARMING RPTS.

1 FOR FORCE ARMING RPTS.

STORE PROGRAM

OPENING AND CLOSING REPORTSThe factory setting does not send opening and closing reports

Alternately, the communicator can be programmed to send an opening report when the system is disarmed, and a closing report when the system is armed for all users, or just the master user.

NOTE 1: For commercial installations using opening and closing reports, it is recommended to disable quick arming to prevent customers from arming the system.

NOTE 2: The reporting codes are fixed for opening and closing. A unique code is reserved for the master user code and each of the five restricted user codes.

NOTE 3: Arming or disarming with the page alert user code dials the supervisory number, no opening or closing report is sent.

PROGRAMMING STEP #111

PROGRAM

0 FOR NO OPEN/CLOSE REPORTS

1 FOR O/C RPTS. FOR ALL USERS

2 FOR O/C RPTS. FROM MASTER USER ONLY

STORE PROGRAM

POINT ID REPORTING

The factory setting enables Point ID and allows the communicator to send two-digit alarm and trouble codes for each sensor. The individual sensor that causes an alarm or trouble report can be identified at the Central Station.

Alternately, Point ID can be disabled. The Central Station will only receive general alarm and trouble reports.

PROGRAMMING STEP #113

PROGRAM

0 FOR GENERAL REPORTS ONLY

1 FOR POINT ID REPORTING

STORE PROGRAM

37