COMMUNICATOR REPORTING CODES

The two-digit communicator reporting code for each event has a factory set value. These values may be customized to fit the specific installation and the reporting requirements of the Central Station monitoring the system.

If Point ID reporting is enabled (the factory
default setting), each sensor can report a unique

HOME = PROGRAM

TEST = REMOVE

alarm and trouble code.

 

 

If Point ID is disabled, the “general” reporting

AWAY

= STORE
codes for each event type will be used.

 

 

Each programming function is performed with similar keystrokes. After the Console is in Setup Mode, enter the programming step number, press the [HOME] key (HOME = program), enter the new value, and press the [AWAY] key (AWAY = store).

Making a value 0 causes event to not communicate to central station.

NOTE: The reporting codes are fixed for opening and closing. A unique code is reserved for the master and the five restricted user codes. See the Opening & Closing Reporting Codes Table.

GENERAL REPORTING CODES

Program Steps #201 - 206 for the communicator reporting codes when Point ID is disabled.

Refer to the Console & General Reporting Codes table to view/edit the reporting codes for each of the five events. The factory settings are listed, along with a blank area to write in the new installation values.

Any value from 0-99 can be programmed for each event (0 = no report).

NOTE: Be careful not to duplicate codes unless the Central Station requires specific codes for certain types of events.

2ABC

PROGRAMMING STEPS

0#201 TO #206

HOME PROGRAM

0 - 99 FOR GENERAL ALARM REPORTING CODE

AWAY STORE PROGRAM

SYSTEM REPORTING CODESProgram Steps #261 - 266 for the Console reporting codes.

Refer to the System Reporting Codes table to view/edit the reporting codes for the keypad [FIRE] and [EMERGENCY] buttons and for each of the four Control Panel conditions. The factory settings are listed, along with a blank area to write in the new installation values.

2 ABC

PROGRAMMING STEPS

6 MNO

#261 TO #266

 

HOME PROGRAM

0 - 99 FOR SYSTEM REPORTING CODE

AWAY STORE PROGRAM

GENERAL REPORTING CODES

STEP #

PROGRAMMING

POSSIBLE

FACTORY

INSTALLATION

FUNCTION

VALUES

VALUE

VALUE

 

 

 

 

 

 

201

GENERAL FIRE REPORT CODE

0 - 99

1

 

202

GENERAL EMERGENCY REPORT CODE

0 - 99

2

 

203

GENERAL SILENT PANIC REPORT CODE

0 - 99

3

 

204

GENERAL BURGLARY REPORT CODE

0 - 99

4

 

206

GENERAL TROUBLE REPORT CODE

0 - 99

6

 

General Reporting Codes Table

38