Maintence and Troubleshooting

Unipro 3.5

K

32 (0)

2300

(1200)

 

 

 

 

N

32 (0)

2300

(1200)

 

 

 

 

NNM

32 (0)

2000

(1100)

 

 

 

 

R

300 (150)

3000

(1800)

 

 

 

 

S

300 (150)

3000

(1800)

 

 

 

 

T

32 (0)

700

(350)

 

 

 

 

 

 

 

 

The usable ranges of the thermocouple types are shown in The table above. If having a high accuracy over a specific operating range is desirable then the input should be calibrated over that range. Follow the calibration procedure for normal calibration with the following changes. Use the low end of the desired range as the zero value and the high end as the span value. There will be more interaction between zero and span with this method. The desired operating range must fit with the limits of the table.

Oxygen /Auxiliary

Board Calibration

Rev. 11.00 December 30, 1995

Page 172
Image 172
Marathon Computer V3.5 user manual Oxygen /Auxiliary Board Calibration