The proportional band is based upon a range of l000. Therefore, if the proportional band is set at 10% and the error is 100 (10% of range) then the output would be 100% (presuming reset=0).

Rate

The rate setting is in minutes and is settable from 0 to 9.99 minutes in .0l steps.

Reset

The reset setting is in repeats per minute. The range is 0 to 99.99 repeats per minute in .0l steps.

Time Proportion

In time proportion mode Output l is ON for the percent of the cycle time when the percent output is plus. When the percent output is minus, Output 2 is ON for the percent of the cycle time.

Unipro 3.5 Process Control