INPUT MODIFICATIONS DEFINED
PRESSURE SWITCH INPUT
The pressure switch is a two level pressure switch. (Figure
During wash fill, the low level of the pressure switch is sensed with 24 VDC and provides an indication to the control board the water level has satisfied the low level. Once satisfied, the 24 VDC circuit is opened. The board then opens the water valve relays and shuts off the water valves.
During rinse fill, the high level provides an indication to the machine control as to whether the high water level has been reached. When the water level switch is satisfied, the pressure switch circuit is opened and power for the water valves is no longer passed through the machine control.
|
|
|
|
|
|
|
|
| Figure 2 |
|
|
TEMPERATURE SENSOR INPUT | DOOR LOCK SWITCH INPUT |
|
| ||
A thermistor is located in the water valve | When input is present, this is indication | ||||
to monitor the blended incoming water | the washer door is locked. The machine | ||||
temperature. The machine control uses | controller will not command the spinner | ||||
this input signal to regulate the water | to tumble or spin when the door lock |
|
| ||
temperature with the warm or cold wash | input is not present. |
|
| ||
and warm rinse temperature selections |
|
|
| ||
(See Water Valve Outputs). |
| If the door is opened during a cycle, | |||
On the MAH7500 model, another | the control will pause the cycle on the | ||||
MAH5500B. |
|
| |||
thermistor is located on the heater |
|
|
| ||
assembly. The machine control board |
|
|
| ||
uses this input signal to maintain the |
|
|
| ||
water temperature in the sump area of |
|
|
| ||
the outer tub, by cycling the heater on/ |
|
| |||
off. |
|
| |||
16010486 |
| Section 2. Washer Controls Overview | |||
|
|
| |||
Revised 02/01 | ©2001 Maytag Appliances Sales Company |
|
|