Terminal Connection Diagram

Sink logic

*1. DC reactor (FR-HEL)

Be sure to connect the DC reactor

Main circuit terminal

supplied with the 75K or more.

When a DC reactor is connected

 

Control circuit terminal

to the 55K or less, remove the

 

jumper across P1-P/+.

 

 

MCCB MC

Three-phase AC power supply

 

Jumper*2

*2. To supply power to the

 

 

control circuit separately,

 

Earth

remove the jumper across

 

(Ground)

R1/L11 and S1/L21.

 

 

Control input signals (No voltage input allowed)

Terminal functions

Forward

rotation

 

 

vary with the input

start

terminal assignment

Reverse

(Pr. 178 to Pr. 189)

rotation

start

 

 

Start self-holding selection

 

High speed

Multi-speed

Middle speed

selection

 

 

 

Low speed

 

Jog mode

Second function selection

*3. AU terminal

 

can be used

Output stop

as PTC input

 

terminal.

Reset

 

 

Terminal 4 input selection (Current input selection)

Selection of automatic restart after instantaneous

power failure Contact input common

*1

(ground)Earth Jumper

 

Jumper

P1

P/+

PR*7 PX*7 N/-

R/L1

 

 

 

S/L2

 

 

 

T/L3

ON

 

 

 

 

Connector for

 

 

 

R1/L11

 

 

with/without

S1/L21

OFF

 

EMC filter *8

Main circuit

Control circuit

STF

 

 

 

STR

 

 

 

STOP

 

 

 

RH

 

 

 

RM

 

 

 

RL

 

 

 

JOG

 

 

 

RT

 

 

 

MRS

 

 

 

RES *3

 

 

 

AU

 

 

 

AU

SOURCE

SINK

 

SD

 

CS PTC

 

 

 

Resistor unit

*6. A CN8 connector is

(Option)

 

 

 

provided with the

 

Brake unit

 

75K or more.

 

(Option)

 

 

 

 

 

 

*7. Do not use PR and PX terminals.

 

 

 

Please do not remove the jumper

CN8*6

 

connected to terminal PR and PX.

 

 

 

U

 

 

 

Motor

 

 

 

 

V

 

 

 

IM

W

 

 

 

 

 

 

 

 

 

 

 

Earth

 

 

 

 

(ground)

 

 

 

 

cable

 

 

*8.The 200V class 0.75K and 1.5K

 

 

 

are not provided with the ON/OFF

 

 

 

connector of the EMC filter.

C1

 

 

 

Relay output

B1

 

 

 

Terminal functions

 

 

Relay output 1

vary with the output

A1

 

(Alarm output)

terminal assignment

 

 

 

 

(Pr. 195, Pr. 196)

C2

 

 

 

 

B2

 

 

 

 

 

 

Relay output 2

A2

 

 

 

 

RUN

 

 

 

Open collector output

 

Running

 

 

 

 

SU

 

 

 

Terminal functions

 

Up to frequency

vary with the output

 

 

IPF

 

Instantaneous

terminal assignment

 

(Pr. 190 to Pr. 194)

 

 

 

 

power failure

 

OL

 

Overload

 

 

 

 

FU

 

 

 

 

 

 

Frequency detection

SE

 

Open collector output common

 

 

Sink/source common

 

 

Features

 

 

 

 

 

 

 

 

Peripheral Devices

Why energy

savings?

 

 

 

 

 

 

 

Standard

Specifications

 

 

 

 

 

 

 

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification

Explanation

 

 

 

 

 

 

 

Operation

Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

List

 

 

 

 

 

 

 

 

 

 

 

 

 

Explanations

of

Parameters

 

 

 

 

 

 

 

Protective

Functions

 

24VDC power supply (Common for external power supply transistor)

PC

PU

 

*9. It is not necessary

 

when calibrating the

 

connector

 

indicator from the

 

 

 

operation panel.

 

 

 

 

Indicator

 

 

 

 

Frequency setting signal (Analog)

10E(+10V)

 

 

 

 

3

 

 

10(+5V)

 

 

Frequency setting

 

 

 

 

 

 

 

2

 

 

0 to 5VDC

 

 

potentiometer

 

 

2

 

 

 

 

 

0 to 10VDC

selected

 

1/2W1k

 

 

 

*4

1

 

 

5

4 to 20mADC

*5

 

 

 

 

 

 

 

 

 

 

(Analog common)

 

 

 

 

 

 

 

 

Auxiliary input (+)

 

 

 

1

0 to ±10VDC

 

 

 

 

0 to ±5VDC selected

*4

 

(-)

 

 

 

 

 

 

 

Terminal 4 input

(+)

 

 

 

4

4 to 20mADC

 

 

 

 

0 to 5VDC

selected

*4

(Current input)

(-)

 

 

 

 

 

 

 

 

0 to 10VDC

 

 

 

 

 

 

 

 

*4. Terminal input

 

 

 

Connector

 

 

 

 

specifications can be

 

 

for plug-in option

 

 

 

 

changed by analog input

 

 

 

 

 

 

connection

 

 

 

 

specifications switchover

 

 

 

 

 

(Pr. 73, Pr. 267).

 

 

 

 

 

 

 

 

*5. It is recommended to use

 

 

 

Option connector 1

2W1kwhen the

 

 

 

 

 

 

 

 

frequency setting signal is

 

 

 

 

 

 

changed frequently.

 

 

 

 

 

 

 

FM

SD

AM 5

TXD+

TXD-

RXD+

RXD-

SG

Terminating resistor VCC

+

 

- (Frequency meter, etc.)

Calibration

 

Moving-coil type

resistor *9

 

1mA full-scale

 

(+)

Analog signal output

 

 

 

(-)

(0 to 10VDC)

 

 

 

 

RS-485 terminals

Data transmission

Data reception

GND

5V (Permissible load current 100mA)

Options

 

 

Instructions

 

 

Motor

 

 

Compatibility

 

Warranty

CAUTION

To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables.

Be sure to use the inverter and motor after grounding (earthing) them.

This connection diagram assumes that the control circuit is sink logic (initial setting). Refer to the instruction manual for the connection in the case of source logic.

Inquiry

 

16

Page 15
Image 15
Mitsubishi Electronics FR-F700 Terminal Connection Diagram, Main circuit, Control circuit, Option connector