Selection of rated sensitivity current of earth (ground) leakage breaker

When using the earth leakage circuit breaker with the inverter circuit, select its rated sensitivity current as follows, independently of the PWM carrier frequency:

Breaker designed for harmonic and surge suppression

Rated sensitivity currentI ∆n ≥ 10 × (Ig1 + Ign + Igi + Ig2 + Igm)

Standard breaker

Rated sensitivity currentI ∆n ≥ 10 × {Ig1 + Ign + Igi + 3 × (Ig2 + Igm)}

Ig1, Ig2

: Leakage currents in wire path during commercial power supply

 

operation

Ign

: Leakage current of inverter input side noise filter

Igm

: Leakage current of motor during commercial power supply operation

Igi

: Inverter unit leakage current

(Note)1. Install the earth leakage breaker (ELB) on the input side of the inverter.

2.In the connection earthed-neutral system, the sensitivity current is purified against an earth (ground) fault in the inverter output side. Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes. (JIS, NEC section 250, IEC 536 class 1 and other applicable standards)

￿Selection example (in the case of the left figure)

 

Breaker Designed for

 

Standard Breaker

 

Harmonic and Surge

 

 

Suppression

 

 

 

Leakage current

1

 

 

5m

Ig1 (mA)

 

 

× 66 ×

 

 

= 0.11

3

 

 

1000m

 

Features

 

 

 

 

 

 

 

Peripheral Devices

Why energy

savings?

 

 

 

 

Standard

Specifications

 

 

 

 

Example of leakage current per 1km during the commercial power supply operation when the CV cable is routed in metal conduit

(Three-phase three-wire delta connection 400V60Hz)

(mA)

100

 

 

 

 

 

 

 

 

 

 

currents

120

 

 

 

 

 

 

 

 

 

 

8 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

leakage

4 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 0

 

 

 

 

 

 

 

 

 

 

2 3.5

 

 

 

8

 

142238

 

 

80150

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.5

3060100

Power supply size (mm2)

Leakage current example of Three-phase induction motor during the commercial power supply operation

(Totally-enclosed fan-cooled type motor 400V60Hz)

(mA)

2. 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

currents

 

 

 

 

 

 

 

 

 

 

 

 

0. 3

 

 

 

 

 

 

 

 

 

 

 

 

 

0. 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

leakage

0. 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0. 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

5

3.

7

7.

5

 

15223755

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0. 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. 2

5.5 1118. 53045

 

Motor capacity (kW)

Leakage current

 

 

 

0 (without noise filter)

 

Ign (mA)

 

 

 

 

 

 

 

 

 

 

 

 

 

Leakage current Igi

 

 

 

1 (Without EMC filter)

 

Refer to the following table for the leakage current of the

(mA)

 

 

 

 

inverter

 

 

 

 

 

 

 

Leakage current

 

1

 

× 66 ×

 

60m

 

= 1.32

Ig2(mA)

3

 

 

1000m

 

 

 

 

Motor leakage

 

 

 

 

0.36

 

 

 

current Igm (mA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total leakage

 

 

2.79

 

 

 

 

6.15

current (mA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated sensitivity

 

 

 

 

 

 

 

 

 

current (mA)(≥ Ig ×

 

 

30

 

 

 

 

100

10)

 

 

 

 

 

 

 

 

 

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification

Explanation

 

 

 

 

 

 

 

Operation

Panel

 

 

 

 

 

 

 

For " " connection, the amount of leakage current is 1/3

example

5.5mm2 5m

5.5mm2 60m

 

ELB

Noise

 

 

 

filter

 

3φ

 

Inverter

IM

 

400V

 

 

 

2.2kW

Ig1

Ign

Ig2

Igm

 

Igi

 

 

￿Inverter leakage current (with and without EMC filter)

Input power conditions

(200V class : 220V/60Hz, 400V class : 440V/60Hz, power supply unbalance within 3%)

 

Voltage

EMC Filter

 

(V)

ON (mA)

OFF (mA)

Phase

200

22(1) *

1

grounding

 

 

 

 

400

30

1

Earthed-neutral

 

 

 

system

 

 

 

 

400

1

1

*For the 200V class 0.75K and 1.5K, the EMC filter is always valid. The leakage current is 1mA.

Parameter

List

 

 

 

 

Explanations of Parameters

 

 

Protective

Functions

 

 

 

 

Options

 

 

 

 

Instructions

 

 

 

 

Motor

 

 

 

 

Compatibility

 

 

Warranty

 

 

 

 

Inquiry

 

 

58

Page 57
Image 57
Mitsubishi Electronics FR-F700 instruction manual Standard Breaker, EMC Filter, On mA