Pr. 338, 339, 550, 551

Operation command source and speed command source during communication operation

Pr.338 Communication operation command source

Pr.339 Communication speed command source

Pr.550 NET mode operation command source selection

Pr.551 PU mode operation command source selection

When the RS-485 terminals or communication option is used, the external operation command and speed command can be

Pr. 503 to 504

To determine the

 

 

 

maintenance time of parts.

 

 

 

 

Features

When the cumulative energization time of the inverter reaches

 

Pr.503 Maintenance timer

Pr.504 Maintenance timer alarm output set time

 

 

the parameter set time, the maintenance timer output signal

 

 

 

 

(Y95) is output.

(MT) is displayed on the operation panel

 

 

PeripheralDevices

Whyenergy savings?

(FR-DU07)

 

 

peripheral devices.

 

 

This can be used as a guideline for the maintenance time of

 

 

made valid. Also, the control command source in the PU operation mode can be selected.

Pr.

Setting

Description

Number

Range

 

 

0

Operation command source communication

338

(initial

value)

 

 

 

 

1

Operation command source external

 

0

 

 

(initial

Speed command source communication

 

value)

 

 

 

Speed command source external (Frequency

339

1

setting from communication is invalid, terminal 2

 

 

and 1 setting from external is valid)

 

 

Speed command source external (Frequency

 

2

setting from communication is valid, terminal 2 and

 

 

1 setting from external is invalid)

 

0

Communication option valid

 

1

Inverter RS-485 terminal valid

550 *

9999

Automatic communication option recognition

 

(initial

Normally, the RS-485 terminals are valid. When

 

the communication option is fitted, the

 

value)

 

communication option is valid.

 

 

 

1

Select the RS-485 terminals as the PU operation

 

mode control source.

 

 

551 *

2

Select the PU connector as the PU operation

 

(initial

 

mode control source.

 

value)

 

 

* Pr. 550 and Pr. 551 are always write-enabled.

Pr.

340

 

Refer to the section about Pr. 79.

 

Pr.

341 to 343

 

Refer to the section about Pr. 117 and

 

 

other relevant parameters.

 

 

 

 

 

Remote output function

Pr. 495 to 497 (REM signal)

Pr.495 Remote output selection

Pr.496 Remote output data 1

Pr.497 Remote output data 2

 

You can utilize the on/off of the inverter's output signals instead of the remote output terminal of the programmable logic controller.

 

First power

ON

 

 

9998

 

 

 

 

(999800h)

 

Set "0" in Pr.503

 

 

 

 

 

Maintenance

 

 

 

timer

Pr.504

 

 

 

(Pr. 503)

 

 

 

 

 

 

 

Time

 

Y95 signal

OFF

ON

ON

 

MT display

 

 

 

￿The cumulative energization time of the inverter is stored into the EEPROM every hour and indicated in Pr. 503 Maintenance timer in 100h increments. Pr. 503 is clamped at 9998 (999800h).

Pr. 549 Refer to the section about Pr.117 to Pr. 124. Pr. 550 to 551 Refer to the section about Pr. 338, Pr.339.

Current average value

Pr. 555 to 557 monitor signal

Pr.555 Current average time

Pr.556 Data output mask time

Pr.557 Current average value monitor signal output reference current

The average value of the output current during constant speed operation and the maintenance timer value are output as a pulse to the current average value monitor signal (Y93).

The pulse width output to the I/O module of the PLC or the like can be used as a guideline due to abrasion of machines and elongation of belt and for aged deterioration of devices to know the maintenance time.

The current average value monitor signal (Y93) is output as pulse for 20s as 1 cycle and repeatedly output during constant speed operation.

From acceleration to constant speed operation

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

Y93 signal

 

 

 

 

 

 

 

1 cycle (20s)

 

 

 

 

 

 

Next cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1) Data output mask time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5) End pulse

When the speed has changed to constant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output as low pulse

from acceleration/deceleration, Y93 signal is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

shape for 1 to 16.5s

not output for Pr.556 time.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4) Maintenance timer pulse

 

 

 

 

 

 

 

 

 

 

 

2) Start pulse

 

 

 

 

 

 

 

 

 

The maintenance timer value (Pr.503) is output

Output as Hi pulse shape for 1s (fixed)

 

 

 

 

 

 

 

 

 

as Hi output pulse shape for 2 to 9s (16000h to

Time and output current set in Pr.555 are averaged

 

 

 

 

 

 

72000h).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.503

1000h

3) Output current average value pulse

 

 

 

 

 

 

 

 

 

Signal output time=

 

 

 

5s

The averaged current value is output as low pulse shape for

 

 

 

 

 

 

 

 

 

 

40000h

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5 to 9s (10 to 180%) during start bit output.

 

 

 

 

 

 

 

 

 

 

 

 

 

output current average value (A)

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal output time=

 

 

 

 

5s

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.557

(A)

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr. 571 Refer to the section about Pr. 13 and other relevant parameters.

Pr.

575 to 577

 

Refer to the section about Pr. 127 and

 

 

other relevant parameters.

 

 

 

 

 

Pr.

611

 

Refer to the section about Pr. 57 and other

 

 

relevant parameters.

 

 

 

Pr. 872 Refer to the section about Pr. 251 and other relevant parameters.

Standard

Specifications

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification

Explanation

 

 

 

 

 

 

 

Operation

Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

List

 

 

 

 

 

 

 

 

 

 

 

 

 

Explanations

of

Parameters

 

 

 

 

 

 

 

Protective

Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compatibility

 

 

 

 

 

 

 

 

 

 

Warranty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inquiry

 

 

 

 

 

 

 

 

Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

44

Page 43
Image 43
Mitsubishi Electronics FR-F700 To determine Maintenance time of parts, Remote output function, Pr to 497 REM signal