Protective Functions
When an alarm occurs in the inverter, the protective function is activated bringing the inverter to an alarm stop and the PU display automatically changes to any of the following error (alarm) indications.
Function Name |
|
| Description | Indication |
Operation panel lock | Appears when operation is tried during operation panel lock. |
| ||
Parameter write error | Appears when an error occurs at parameter writing. | to | ||
| ||||
|
|
|
|
|
Copy operation error | Appears when an error occurs at parameter copying. | to | ||
| ||||
|
|
|
| |
Error | Appears when the RES signal is on or the PU and inverter can not make normal |
| ||
communication. |
|
| ||
Stall Prevention |
|
| ||
Appears during overcurrent stall prevention. |
| |||
(overcurrent) |
| |||
|
|
|
| |
Stall prevention | Appears during overvoltage stall prevention |
| ||
(overvoltage) | Appears while the regeneration avoidance function is activated. |
| ||
| Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 "special |
| ||
Regenerative brake | regenerative brake duty" value. If the regenerative brake duty reaches 100%, a |
| ||
prealarm | regenerative overvoltage (E. OV_) occurs. |
| ||
| (displayed only for the 75K or more) |
| ||
Electronic thermal relay | Appears when the electronic thermal O/L relay has reached 85% of the specified |
| ||
function prealarm | value. |
|
| |
PU Stop | Appears when |
| on the operation panel was pressed during external operation. |
|
|
| |||
Maintenance signal output | Appears when the cumulative energization time has exceeded the maintenance |
| ||
output timer set value. |
| |||
|
| |||
Parameter copy | Appears when parameters are copied between models with capacities of 55K or |
| ||
less and 75K or more. |
| |||
|
| |||
Fan fault | Appears when the cooling fan remains stopped when operation is required or when the speed |
| ||
has decreased. |
|
| ||
|
|
| ||
Overcurrent | Appears when an overcurrent occurred during acceleration. |
| ||
acceleration |
| |||
|
|
|
| |
Overcurrent | Appears when an overcurrent occurred during constant speed operation. |
| ||
constant speed |
| |||
|
|
|
| |
Overcurrent | Appears when an overcurrent occurred during deceleration and at a stop. |
| ||
deceleration or stop |
| |||
|
|
|
| |
Regenerative overvoltage | Appears when an overvoltage occurred during acceleration. |
| ||
shutoff during acceleration |
| |||
|
|
|
| |
Regenerative overvoltage |
|
|
|
|
Appears when an overvoltage occurred during constant speed operation. |
| |||
speed |
|
|
|
|
Regenerative overvoltage shut- | Appears when an overvoltage occurred during deceleration and at a stop. |
| ||
off during deceleration or stop |
|
|
|
|
Inverter overload | Appears when the electronic thermal relay function for inverter element protection |
| ||
(electronic thermal relay |
| |||
was activated. |
|
| ||
function)*1 |
|
| ||
|
|
|
| |
Motor overload | Appears when the electronic thermal relay function for motor protection was |
| ||
(electronic thermal relay |
| |||
activated. |
|
| ||
function)*1 |
|
| ||
|
|
|
| |
Fin overheat | Appears when the heatsink overheated. |
| ||
Instantaneous power failure | Appears when an instantaneous power failure occurred at an input power supply. |
| ||
protection |
| |||
|
|
|
| |
Undervoltage protection | Appears when the main circuit DC voltage became low. |
| ||
Input phase failure | Appears if one of the three phases on the inverter input side opened. |
| ||
Stall prevention | Appears when the output frequency drops to 0.5Hz as a result of deceleration due to |
| ||
the excess motor load. |
| |||
|
| |||
Output side earth (ground) | Appears when an earth (ground) fault occurred on the inverter's output side. |
| ||
fault overcurrent protection |
| |||
|
|
|
| |
Output phase failure | Appears if one of the three phases on the inverter output side opened. |
| ||
protection |
| |||
|
|
|
| |
External thermal relay | Appears when the external thermal relay connected to the terminal OH operated. |
| ||
operation *6 |
| |||
|
|
|
| |
PTC thermistor operation | Appears when the motor overheat status is detected for 10s or more by the external |
| ||
PTC thermistor input connected to the terminal AU. |
| |||
|
| |||
| Appears when an alarm occurred in the option card or an AC power supply is |
| ||
Option alarm | connected to the R/L1, S/L2, T/L3 when the high power factor converter connection |
| ||
| is set. |
|
| |
Option slot alarm | Appears when a communication error occurred in the communication option. |
| ||
Option alarm | Appears when a functional error occurred in the |
| ||
Parameter storage devide | Appears when operation of the element where parameters are stored became |
| ||
alarm | abnormal. (control circuit board) |
|