Parameter List
For simple
POINT
Only simple mode parameters are displayed by the initial setting of Pr.160 User group read selection. Set Pr.160 User group read selection as required.
Simple mode parameter
Parameter | Name | Range | Increments | Initial Value | Refer to | |
Number | page | |||||
|
|
|
| |||
0 | Torque boost | 0 to 30% | 0.1% | 6/4/3/2/1.5/1%*2 | 28 | |
1 | Maximum frequency | 0 to 120Hz | 0.01Hz | 120/60Hz*1 | 28 | |
2 | Minimum frequency | 0 to 120Hz | 0.01Hz | 0Hz | 28 | |
3 | Base frequency | 0 to 400Hz | 0.01Hz | 60Hz | 28 | |
4 | 0 to 400Hz | 0.01Hz | 60Hz | 28 | ||
5 | 0 to 400Hz | 0.01Hz | 30Hz | 28 | ||
6 | 0 to 400Hz | 0.01Hz | 10Hz | 28 | ||
7 | Acceleration time | 0 to 3600/ 360s | 0.1/0.01s | 5s/15s*3 | 28 | |
8 | Deceleration time | 0 to 3600/ 360s | 0.1/0.01s | 10s/30s*3 | 28 | |
9 | Electronic thermal O/L relay | 0 to 500/ 0 to 3600A*1 | 0.01/0.1A*1 | Rated inverter | 29 | |
output current | ||||||
|
|
|
|
| ||
60 | Energy saving control selection | 0, 4, 9 | 1 | 0 | 34 | |
79 | Operation mode selection | 0, 1, 2, 3, 4, 6, 7 | 1 | 0 | 37 | |
125 | Terminal 2 frequency setting gain frequency | 0 to 400Hz | 0.01Hz | 60Hz | 39 | |
126 | Terminal 4 frequency setting gain frequency | 0 to 400Hz | 0.01Hz | 60Hz | 39 | |
160 | User group read selection | 0, 1, 9999 | 1 | 9999 | 40 |
Extended mode parameter
Remarks
⋅The parameters marked with indicate simple mode parameters.
⋅The shaded parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in Pr. 77 Parameter write selection.
Function | Parameters | Name | Setting Range | Increments | Initial Value | Refer to | |
page | |||||||
|
|
|
|
|
| ||
| 0 | Torque boost | 0 to 30% | 0.1% | 6/4/3/2/1.5/1%*2 | 28 | |
| 1 | Maximum frequency | 0 to 120Hz | 0.01Hz | 120/60Hz*1 | 28 | |
functions | 2 | Minimum frequency | 0 to 120Hz | 0.01Hz | 0Hz | 28 | |
5 | 0 to 400Hz | 0.01Hz | 30Hz | 28 | |||
| 3 | Base frequency | 0 to 400Hz | 0.01Hz | 60Hz | 28 | |
| 4 | 0 to 400Hz | 0.01Hz | 60Hz | 28 | ||
Basic |
|
|
|
|
|
| |
6 | 0 to 400Hz | 0.01Hz | 10Hz | 28 | |||
7 | Acceleration time | 0 to 3600/ 360s | 0.1/0.01s | 5s/15s*3 | 28 | ||
| 8 | Deceleration time | 0 to 3600/ 360s | 0.1/0.01s | 10s/30s*3 | 28 | |
| 9 | Electronic thermal O/L relay | 0 to 500/ 0 to 3600A*1 | 0.01/0.1A*1 | Rated inverter | 29 | |
| output current | ||||||
|
|
|
|
|
| ||
InjectionDC Brake | 10 | DC injection brake operation frequency | 0 to 120Hz, 9999 | 0.01Hz | 3Hz | 29 | |
11 | DC injection brake operation time | 0 to 10s | 0.1s | 0.5s | 29 | ||
| |||||||
| 12 | DC injection brake operation voltage | 0 to 30% | 0.1% | 4/2/1%*4 | 29 | |
|
|
|
|
|
|
| |
| 13 | Starting frequency | 0 to 60Hz | 0.01Hz | 0.5Hz | 29 | |
| 14 | Load pattern selection | 0, 1 | 1 | 1 | 29 | |
Jog operation | 15 | Jog frequency | 0 to 400Hz | 0.01Hz | 5Hz | 29 | |
16 | Jog acceleration/deceleration time | 0 to 3600/360s | 0.1/0.01s | 0.5s | 29 | ||
| |||||||
|
|
|
|
|
|
|
*1 Differ according to capacities. (55K or less/75K or more)
*2 Differ according to capacities. (0.75K/1.5K to 3.7K/5.5K, 7.5K/11K to 37K/45K, 55K/75K or more) *3 Differ according to capacities. (7.5K or less/11K or more)
*4 Differ according to capacities. (7.5K or less/11K to 55K/75K or more)
21