Pr. 57, 58, 162 to 165, 299, 611
Restart operation after instantaneous power failure / Flying start
Pr.57 Restart coasting time | Pr.58 Restart cushion time |
Pr.162 Automatic restart after instantaneous power failure selection | |
Pr.163 First cushion time for restart |
|
Pr.164 First cushion voltage for restart | Pr.165 Stall prevention operation level for restart |
Pr.299 Rotation direction detection selection at restarting
Pr.611 Acceleration time at a restart
You can restart the inverter without stopping the motor in the following cases.
⋅when commercial power supply operation is switched to inverter operation
⋅when power comes back on after an instantaneous power failure
⋅when motor is coasting at start
Pr. | Setting Range | Description | |
Number | |||
|
| ||
|
| 1.5K or less..........0.5s, | |
| 0 | 2.2K to 7.5K.........1s, | |
| 11K or more ........3.0s | ||
57 |
| 75K or more ........5.0s | |
| The above times are coasting time. | ||
|
| ||
| 0.1 to 5s/ | Set the waiting time for | |
| restart after an instantaneous power | ||
| 0.1 to 30s * | ||
| failure. | ||
|
| ||
| 9999 (initial value) | No restart | |
58 | 0 to 60s | Set a voltage starting time at restart. | |
| 0 (initial value) | With frequency search | |
| 1 | Without frequency search (reduced | |
162 | voltage system) | ||
| |||
| 10 | Frequency search at every start | |
| 11 | Reduced voltage system at every start | |
163 | 0 to 20s | Set a voltage starting time at restart. | |
|
| Consider using these parameters | |
164 | 0 to 100% | according to the load (inertia moment, | |
|
| torque) magnitude. | |
165 | 0 to 150% | Consider the rated inverter current as | |
100% and set the stall prevention | |||
|
| operation level during restart operation. | |
| 0 | Without rotation direction detection | |
| 1 | With rotation direction detection | |
299 |
| When Pr. 78 =0, the rotation direction is | |
9999 | detected. | ||
| |||
| When Pr. 78 =1,2, the rotation direction is | ||
|
| ||
|
| not detected. | |
| 0 to 3600s | Set the acceleration time to reach the set | |
611 | frequency at restart. | ||
| |||
9999 | Acceleration time for restart is the normal | ||
| |||
| acceleration time (e.g. Pr. 7). | ||
|
|
*The setting range varies according to the inverter capacity. (55K or less/ 75K or more)
<Connection diagram>
|
|
| MC2 |
MCCB | MC1 |
| MC3 |
| R/L1 | U | |
|
| ||
| S/L2 | V | IM |
| T/L3 | W |
|
| R1/L11 |
|
|
| S1/L21 |
|
|
STF |
|
CS | MC |
SD | switchover |
| sequence |
For use for only
CS automatic restart
SD after instantaneous power failure or flying start, short
When “0 (initial value) or 10” is set in Pr. 162, the inverter smoothly starts after detecting the motor speed upon power restoration.
Even when the motor is rotating in the opposite direction, the inverter can be restarted smoothly as the direction of rotation is detected. (You can select whether to make rotation direction detection or not with Pr. 299 Rotation direction detection selection at restarting. )
When Pr. 162 = 0, 10 (with frequency search)
Instantaneous (power failure) time
Power supply (R/L1,S/L2,T/L3)
Motor
speed N (r/min) Inverter
output frequency |
| * |
|
|
|
| |
f (Hz) |
|
|
|
Inverter |
|
|
|
output voltage |
|
|
|
E (V) |
|
| Restart cushion |
|
|
| |
Coasting | + | Speed | time (Pr. 58 setting) |
time (Pr.57) | detection time |
|
Acceleration time at a restart
(Pr. 611 setting)
*The output shut off timing differs according to the load condition.
When Pr. 162 = "1" or "11", automatic restart operation is performed in a reduced voltage system, where the voltage is gradually risen with the output frequency unchanged from prior to an instantaneous power failure independently of the coasting speed of the motor.
When Pr. 162 = 1, 11 (without frequency search)
Instantaneous (power failure) time
Power supply (R/L1,S/L2,T/L3)
Motor speed N |
|
|
|
|
| |
(r/min) |
|
|
|
|
| |
|
|
|
|
|
|
|
Inverter |
| * |
|
|
| |
output frequency |
|
|
|
| ||
|
|
|
|
| ||
f (Hz) |
|
|
|
|
|
|
Inverter |
|
|
|
|
| |
|
|
|
|
| ||
output voltage |
|
|
|
|
|
|
E (V) |
|
|
|
|
|
Coasting time |
|
|
|
|
| ||
Pr. 57 setting | Restart cushion | ||
|
| time |
Pr. 58 setting
*The output shut off timing differs according to the load condition.
Pr. 59 Remote setting function
Pr.59 Remote function selection
Even if the operation panel is located away from the enclosure, you can use contact signals to perform continuous
By merely setting this parameter, you can use the acceleration, deceleration and setting clear functions of the motorized speed setter
Pr.59 Setting | Description | ||
RH, RM, RL signal | Frequency setting | ||
| function | storage function | |
0 (initial value) |
| | |
1 | Remote setting | Yes | |
2 | Remote setting | No | |
|
| No | |
3 | Remote setting | (Turning STF/STR off | |
clears | |||
|
| ||
|
| frequency.) |
frequency |
| When Pr. 59 = 1, 2 | When Pr. 59 = 1 | ||
| When Pr. 59 = 3 |
| |||
|
| When Pr. 59 = 2, 3 | |||
* |
|
|
| ||
Output (Hz) |
|
|
|
| |
| 0Hz |
|
| Time | |
Acceleration | ON |
| ON |
| |
(RH) | ON |
|
|
| |
Deceleration | ON |
|
|
| |
(RM) |
|
|
| ||
| ON |
|
| ||
Clear (RL) |
|
|
| ||
|
|
|
| ||
Forward | ON | ON | ON | ON | |
rotation (STF) | |||||
|
|
|
| ||
Power supply | ON |
|
| ON |
*External runnning frequency (other than
33 | Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions. |