Pr. Noise elimination at the analog 74 input
Pr.74 Input filter time constant
The time constant of the primary delay filter relative to external frequency command (analog input (terminal 1, 2, 4) signal) can be set.
Valid for eliminating noise of the frequency setting circuit.
Increase the filter time constant if steady operation cannot be performed due to noise.
A larger setting results in slower response. (The time constant can be set between approximately 10ms to 1s with the setting of 0 to 8.)
Pr. Reset selection, disconnected PU 75 detection
Pr.75 Reset selection/disconnected PU detection/PU stop selection
You can select the reset input acceptance, disconnected PU
Pr.75 | Reset Selection | Disconnected | PU Stop | |||
Setting | PU Detection | Selection | ||||
| ||||||
0 | Reset input normally | If the PU is |
|
|
| |
enabled. |
|
|
| |||
| disconnected, |
|
|
| ||
| Reset input enabled |
|
|
| ||
1 | operation will be | Pressing |
|
| ||
only when the protective | continued |
|
| |||
| function is activated. |
| decelerates the | |||
2 | Reset input normally | When the PU is | motor to a stop only | |||
enabled. | disconnected, | in the PU operation | ||||
| ||||||
| Reset input enabled | the inverter | mode. | |||
3 | only when the protective | output is shut |
|
|
| |
| function is activated. | off. |
|
|
| |
14 | Reset input normally |
|
|
|
| |
(initial | If the PU is |
|
|
| ||
enabled. |
|
|
| |||
value) | disconnected, |
|
|
| ||
| Pressing |
|
| |||
| Reset input enabled | operation will be |
|
| ||
| decelerates the | |||||
15 | only when the protective | continued | ||||
| function is activated. |
| motor to a stop in | |||
| Reset input normally | When the PU is | any of the PU, | |||
16 | external and | |||||
| enabled. | disconnected, | communication | |||
| Reset input enabled | the inverter | operation modes. | |||
17 | only when the protective | output is shut |
|
|
| |
| function is activated. | off. |
|
|
|
Reset selection
⋅You can select the operation timing of reset function (RES signal, reset command through communication) input
Disconnected PU detection
⋅This function detects that the PU
PU stop selection
⋅In any of the PU operation, external operation and network
operation modes, the motor can be stopped by pressing of the PU.
Pr. 76 Output function of alarm code
Pr.76 Alarm code output selection
At alarm occurrence, its description can be output as a
The alarm code can be read by a programmable controller, etc., and its corrective action can be shown on a display, etc.
Pr.76 Setting | Description |
0 (initial value) | Without alarm code output |
1With alarm code output (Refer to the following table)
2Alarm code output at alarm occurrence only (Refer to the following table)
The following table indicates alarm codes to be output. (0: output
transistor off, 1: output transistor on)
Operation Panel | Output of Output Terminals | Alarm Code | ||||
Indication |
|
|
|
| ||
SU | IPF | OL | FU | |||
| ||||||
|
|
|
|
| ||
Normal * | 0 | 0 | 0 | 0 | 0 | |
E.OC1 | 0 | 0 | 0 | 1 | 1 | |
E.OC2 | 0 | 0 | 1 | 0 | 2 | |
E.OC3 | 0 | 0 | 1 | 1 | 3 | |
E.OV1 to E.OV3 | 0 | 1 | 0 | 0 | 4 | |
E.THM | 0 | 1 | 0 | 1 | 5 | |
E.THT | 0 | 1 | 1 | 0 | 6 | |
E.IPF | 0 | 1 | 1 | 1 | 7 | |
E.UVT | 1 | 0 | 0 | 0 | 8 | |
E.FIN | 1 | 0 | 0 | 1 | 9 | |
E.BE | 1 | 0 | 1 | 0 | A | |
E. GF | 1 | 0 | 1 | 1 | B | |
E.OHT | 1 | 1 | 0 | 0 | C | |
E.OLT | 1 | 1 | 0 | 1 | D | |
E.OPT | 1 | 1 | 1 | 0 | E | |
E.OP1 | 1 | 1 | 1 | 0 | E | |
Other than the | 1 | 1 | 1 | 1 | F | |
above | ||||||
|
|
|
|
|
*When Pr. 76 = "2", the output terminals output the signals assigned to Pr. 190 to Pr. 196.
Pr. 77 Prevention of parameter rewrite
Pr.77 Parameter write selection
You can select whether write to various parameters can be performed or not. Use this function to prevent parameter values from being rewritten by misoperation.
Pr. 77 Setting | Description |
0 (initial value) | Write is enabled only during a stop |
|
|
1Parameter write is not enabled.
2Parameter write is enabled in any operation mode regardless of operation status.
Pr. Prevention of reverse rotation of 78 the motor
Pr.78 Reverse rotation prevention selection
This function can prevent reverse rotation fault resulting from the incorrect input of the start signal.
Pr.78 Setting | Description |
0 (initial value) | Both forward and reverse rotations allowed |
|
|
1Reverse rotation disabled
2Forward rotation disallowed
|
| Features |
|
| |
|
|
| |||
|
|
| |||
Peripheral Devices | Why energy | savings? | |||
|
|
|
|
|
|
| Standard | Specifications |
| ||
|
|
|
|
|
|
Outline | Dimension | Drawings | |||
|
|
|
|
|
|
|
|
|
|
|
|
Terminal Connection | Diagram | Terminal Specification | Explanation | ||
|
|
|
|
|
|
| Operation | Panel |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| Parameter | List |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
Explanations | of | Parameters | |||
|
|
|
|
|
|
| Protective | Functions |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Options |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Instructions |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Motor |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Compatibility |
|
| |
|
|
|
|
|
|
|
| Warranty |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Inquiry |
|
| |
|
|
|
|
|
|
Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions. | 36 |