Pr. Noise elimination at the analog 74 input

Pr.74 Input filter time constant

The time constant of the primary delay filter relative to external frequency command (analog input (terminal 1, 2, 4) signal) can be set.

￿Valid for eliminating noise of the frequency setting circuit.

￿Increase the filter time constant if steady operation cannot be performed due to noise.

A larger setting results in slower response. (The time constant can be set between approximately 10ms to 1s with the setting of 0 to 8.)

Pr. Reset selection, disconnected PU 75 detection

Pr.75 Reset selection/disconnected PU detection/PU stop selection

You can select the reset input acceptance, disconnected PU (FR-DU07) connector detection function and PU stop function.

Pr.75

Reset Selection

Disconnected

PU Stop

Setting

PU Detection

Selection

 

0

Reset input normally

If the PU is

 

 

 

enabled.

 

 

 

 

disconnected,

 

 

 

 

Reset input enabled

 

 

 

1

operation will be

Pressing

 

 

only when the protective

continued as-is.

 

 

 

function is activated.

 

decelerates the

2

Reset input normally

When the PU is

motor to a stop only

enabled.

disconnected,

in the PU operation

 

 

Reset input enabled

the inverter

mode.

3

only when the protective

output is shut

 

 

 

 

function is activated.

off.

 

 

 

14

Reset input normally

 

 

 

 

(initial

If the PU is

 

 

 

enabled.

 

 

 

value)

disconnected,

 

 

 

 

Pressing

 

 

 

Reset input enabled

operation will be

 

 

 

decelerates the

15

only when the protective

continued as-is.

 

function is activated.

 

motor to a stop in

 

Reset input normally

When the PU is

any of the PU,

16

external and

 

enabled.

disconnected,

communication

 

Reset input enabled

the inverter

operation modes.

17

only when the protective

output is shut

 

 

 

 

function is activated.

off.

 

 

 

￿Reset selection

You can select the operation timing of reset function (RES signal, reset command through communication) input

￿Disconnected PU detection

This function detects that the PU (FR-DU07/FR-PU04) has been disconnected from the inverter for longer than 1s and causes the inverter to provide an alarm output (E.PUE) and come to an alarm stop.

￿PU stop selection

In any of the PU operation, external operation and network

operation modes, the motor can be stopped by pressing of the PU.

Pr. 76 Output function of alarm code

Pr.76 Alarm code output selection

At alarm occurrence, its description can be output as a 4-bit digital signal from the open collector output terminals.

The alarm code can be read by a programmable controller, etc., and its corrective action can be shown on a display, etc.

Pr.76 Setting

Description

0 (initial value)

Without alarm code output

1With alarm code output (Refer to the following table)

2Alarm code output at alarm occurrence only (Refer to the following table)

￿The following table indicates alarm codes to be output. (0: output

transistor off, 1: output transistor on)

Operation Panel

Output of Output Terminals

Alarm Code

Indication

 

 

 

 

SU

IPF

OL

FU

(FR-DU07)

 

 

 

 

 

 

Normal *

0

0

0

0

0

E.OC1

0

0

0

1

1

E.OC2

0

0

1

0

2

E.OC3

0

0

1

1

3

E.OV1 to E.OV3

0

1

0

0

4

E.THM

0

1

0

1

5

E.THT

0

1

1

0

6

E.IPF

0

1

1

1

7

E.UVT

1

0

0

0

8

E.FIN

1

0

0

1

9

E.BE

1

0

1

0

A

E. GF

1

0

1

1

B

E.OHT

1

1

0

0

C

E.OLT

1

1

0

1

D

E.OPT

1

1

1

0

E

E.OP1

1

1

1

0

E

Other than the

1

1

1

1

F

above

 

 

 

 

 

*When Pr. 76 = "2", the output terminals output the signals assigned to Pr. 190 to Pr. 196.

Pr. 77 Prevention of parameter rewrite

Pr.77 Parameter write selection

You can select whether write to various parameters can be performed or not. Use this function to prevent parameter values from being rewritten by misoperation.

Pr. 77 Setting

Description

0 (initial value)

Write is enabled only during a stop

 

 

1Parameter write is not enabled.

2Parameter write is enabled in any operation mode regardless of operation status.

Pr. Prevention of reverse rotation of 78 the motor

Pr.78 Reverse rotation prevention selection

This function can prevent reverse rotation fault resulting from the incorrect input of the start signal.

Pr.78 Setting

Description

0 (initial value)

Both forward and reverse rotations allowed

 

 

1Reverse rotation disabled

2Forward rotation disallowed

 

 

Features

 

 

 

 

 

 

 

 

Peripheral Devices

Why energy

savings?

 

 

 

 

 

 

 

Standard

Specifications

 

 

 

 

 

 

 

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification

Explanation

 

 

 

 

 

 

 

Operation

Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

List

 

 

 

 

 

 

 

 

 

 

 

 

 

Explanations

of

Parameters

 

 

 

 

 

 

 

Protective

Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compatibility

 

 

 

 

 

 

 

 

 

 

Warranty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inquiry

 

 

 

 

 

 

 

 

Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

36

Page 35
Image 35
Mitsubishi Electronics FR-F700 Pr. Noise elimination at the analog 74 input, Pr Output function of alarm code