25
Input terminal function assignment
178 STF terminal function selection
0 to 8, 10 to 12, 14, 16,
24, 25, 60, 62, 64 to 67,
9999
160 41
179 STR terminal function selection
0 to 8, 10 to 12, 14, 16,
24, 25, 61, 62, 64 to 67,
9999
161 41
180 RL terminal function selection
0 to 8, 10 to 12, 14, 16,
24, 25, 62, 64 to 67, 9999
1 0 41
181 RM terminal function selection 1 1 41
182 RH terminal function selection 1 2 41
183 RT terminal function selection 1 3 41
184 AU terminal function selection 0 to 8, 10 to 12, 14, 16,
24, 25, 62 to 67, 9999 1 4 41
185 JOG terminal function selection
0 to 8, 10 to 12, 14, 16,
24, 25, 62, 64 to 67, 9999
1 5 41
186 CS terminal function selection 1 6 41
187 MRS terminal function selection 124 41
188 STOP terminal function selection 125 41
189 RES terminal function selection 162 41
Output terminal
function assignment
190 RUN terminal function selection 0 to 5, 7, 8, 10 to 19, 25,
26, 45 to 47, 64, 70, 90 to
96, 98, 99, 100 to 105,
107, 108, 110 to 116, 125,
126, 145 to 147, 164, 170,
190 to 196, 198, 199, 9999
1 0 41
191 SU terminal function selection 1 1 41
192 IPF terminal function selection 1 2 41
193 OL terminal function selection 1 3 41
194 FU terminal function selection 1 4 41
195 ABC1 terminal function selection 0 to 5, 7, 8, 10 to 19, 25,
26, 45 to 47, 64, 70, 90,
91, 94 to 96, 98, 99, 100 to
105, 107, 108, 110 to 116,
125, 126, 145 to 147, 164,
170, 190, 191, 194 to 196,
198, 199, 9999
199 41
196 ABC2 terminal function selection 19999 41
Multi-speed
setting
232 to 239 Multi-speed setting 8 speed to 15 speed 0 to 400Hz, 9999 0.01Hz 9999 28
240 Soft-PWM operation selection 0, 1 1 1 35
241 Analog input display unit switchover 0, 1 1 0 39
242 Terminal 1 added compensation amount
(terminal 2) 0 to 100% 0.1% 100% 35
243 Terminal 1 added compensation amount
(terminal 4) 0 to 100% 0.1% 75% 35
244 Cooling fan operation selection 0, 1 1 1 42
Slip
compensation
245 Rated slip 0 to 50%, 9999 0.01% 9999 42
246 Slip compensation time constant 0.01 to 10s 0.01s 0.5s 42
247 Constant-output region slip
compensation selection 0, 9999 19999 42
250 Stop selection 0 to 100s, 1000 to 1100s,
8888, 9999 0.1s 9999 42
251 Output phase failure protection
selection 0, 1 1 1 42
Frequency
compensation
function
252 Override bias 0 to 200% 0.1% 50% 35
253 Override gain 0 to 200% 0.1% 150% 35
Life check
255 Life alarm status display (0 to 15) 1 0 42
256 Inrush current limit circuit life display (0 to 100%) 1% 100% 42
257 Control circuit capacitor life display (0 to 100%) 1% 100% 42
258 Main circuit capacitor life display (0 to 100%) 1% 100% 42
259 Main circuit capacitor life measuring 0, 1 1 0 42
260 PWM frequency automatic switchover 0, 1 1 1 35
Function
Parameters
Name Setting Range Increments Initial Value
Refer to
page