Pr. 79 Pr. 340 Operation mode selection
Pr.79 Operation mode selection Pr.340 Communication startup mode selection
Used to select the operation mode of the inverter.
You can freely change between operation by external signal (external operation), operation by PU
Pr.79 |
|
|
|
| LED Indication | |||
Description |
|
|
| :Off | ||||
Setting |
|
|
| |||||
|
|
|
|
| :On | |||
|
|
|
|
|
| |||
| External/PU switchover mode ( Press | External operation | ||||||
| mode |
|
| |||||
0 |
|
|
|
|
|
| ||
to switch between the PU and | PU | EXT | NET | |||||
(initial | ||||||||
|
|
|
| PU operation mode | ||||
value) | external operation mode.) |
|
| |||||
| External operation mode at | PU | EXT | NET | ||||
1 | Fixed to PU operation mode |
| PU | EXT | NET | |||
|
|
|
|
| External operation | |||
| Fixed to external operation mode |
| mode |
|
| |||
|
| PU | EXT | NET | ||||
2 | Operation can be performed by switching | |||||||
NET operation | ||||||||
between the external and Net operation | ||||||||
| ||||||||
| mode. |
|
|
| mode |
|
| |
|
|
|
|
| PU | EXT | NET | |
| External/PU combined operation mode 1 |
|
|
| ||||
| Running frequency | Start signal |
|
|
| |||
| PU |
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
3 | or external signal | External signal |
|
|
| |||
| input | input (terminal STF, |
|
|
| |||
| setting, across |
|
|
| ||||
| STR) |
|
|
|
|
| ||
| terminals |
|
|
|
|
| ||
|
|
|
|
|
|
| ||
| when AU signal |
|
|
| PU | EXT | NET | |
| turns on)) |
|
|
| ||||
|
|
|
|
|
|
| ||
| External/PU combined operation mode 2 |
|
|
| ||||
| Running frequency | Start signal |
|
|
| |||
4 | External signal | Input from the PU |
|
|
| |||
|
|
| ||||||
| input (terminal 2, 4, | PU04) |
|
|
|
| ||
| 1, Jog, |
|
|
|
| |||
|
|
|
|
|
|
| ||
| setting, etc) | ( | , | ) |
|
|
| |
|
|
|
|
| PU operation mode | |||
|
|
|
|
| PU | EXT | NET | |
|
|
|
| External operation | ||||
|
|
|
| mode |
|
| ||
6 | Switch among PU operation, external |
|
| |||||
|
|
| ||||||
operation, and NET operation while | PU | EXT | NET | |||||
| ||||||||
| keeping the same operation status. | NET operation | ||||||
|
|
|
|
| mode |
|
| |
|
|
|
|
| PU | EXT | NET | |
| External operation mode (PU operation | PU operation mode | ||||||
| interlock) |
|
|
| ||||
| X12 signal ON |
|
|
| PU | EXT | NET | |
7 | Operation mode can be switched to the | External operation | ||||||
PU operation mode. |
|
| ||||||
|
| mode |
|
| ||||
| (output stop during external operation) |
|
| |||||
|
|
|
| |||||
| X12 signal OFF |
|
|
| PU | EXT | NET | |
| Operation mode can not be switched to |
|
|
| ||||
| the PU operation mode. |
|
|
|
|
|
Specify operation mode at power on (Pr.340)
⋅When power is switched on or when power comes back on after instantaneous power failure, the inverter can be started up in the network operation mode.
After the inverter has started up in the network operation mode, parameter write and operation can be performed from a program. Set this mode for communication operation using the inverter RS- 485 terminals or communication option.
⋅You can set the operation mode at power on (reset) according to the Pr. 79 and Pr. 340 settings.
Pr. 340 | Pr.79 | Operation mode at | Operation Mode | |
Power On, Power | ||||
Setting | Setting | Switchover | ||
Restoration, Reset | ||||
|
|
| ||
0 |
|
|
| |
(initial | As set in Pr. 79. |
| ||
value) |
|
|
| |
| 0 | NET operation mode | Can be switched to external, | |
| PU or NET operation mode *2 | |||
|
|
| ||
| 1 | PU operation mode | Fixed to PU operation mode | |
|
|
| Can be switched to external | |
| 2 | NET operation mode | or NET operation mode | |
| Switching to PU operation | |||
|
|
| ||
|
|
| mode disabled | |
| 3, 4 | External/PU combined | Operation mode switching | |
1, 2 *1 | operation mode | disabled | ||
| ||||
| 6 | NET operation mode | Can be switched to external, | |
| PU or NET operation mode | |||
|
|
| with operation continued | |
|
| X12 (MRS) signal ON | Can be switched to external, | |
|
| .. NET operation mode | PU or NET operation mode *2 | |
| 7 | X12(MRS)signal OFF | Fixed to external operation | |
|
| .. External operation | mode (Forcibly switched to | |
|
| mode | external operation mode.) | |
| 0 | NET operation mode | Can be switched to PU or | |
| NET operation mode *3 | |||
|
|
| ||
| 1 | PU operation mode | Fixed to PU operation mode | |
| 2 | NEToperation mode | Fixed to NET operation mode | |
| 3, 4 | External/PU combined | Operation mode switching is | |
10, 12 | operation mode | disallowed | ||
| ||||
*1 | 6 | NET operation mode | Can be switched to PU or | |
| NET operation mode with | |||
|
|
| operation continued *3 | |
| 7 | External operation | Fixed to external operation | |
| mode (Forcibly switched to | |||
| mode | |||
|
| external operation mode.) | ||
|
|
|
*1 The Pr. 340 setting "2" or "12" is mainly used for communication operation using the inverter
When a value other than "9999" (selection of automatic restart after instantaneous power failure) is set in Pr. 57 Restart coasting time, the inverter will resume the same operation state which was in before after power has been restored from an instantaneous power failure.
*2 The operation mode cannot be switched directly between the PU operation mode and network operation mode.
*3 Operation mode can be changed between the PU operation mode and
network operation mode with key of the operation panel (FR- DU07) and X65 signal.
Pr. Simple magnetic flux vector 80, 90 control
Pr.80 Motor capacity (simple magnetic flux vector control)
Pr.90 Motor constant (R1)
Providing optimum excitation to the motor can also produce high torque in a
⋅Set the used motor capacity (equal to or one rank higher than the inveter capacity) in Pr. 80.
⋅The number of motor poles should be any of 2, 4 and 6 poles.
⋅
⋅Wiring length from inverter to motor should be within 30m.
⋅When simple magnetic flux vector control is not used, set "9999" (initial value) in Pr. 80.
⋅For Pr. 90 Motor constant (R1), normally setting is not necessary. When you need more torque under simple magnetic flux vector control for other manufacturer's motor, set the motor primary resistance value (R1) for connection in Pr. 90
37 | Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions. |