Pr. 79 Pr. 340 Operation mode selection

Pr.79 Operation mode selection Pr.340 Communication startup mode selection

￿Used to select the operation mode of the inverter.

You can freely change between operation by external signal (external operation), operation by PU (FR-DU07) (PU operation), operation by combination of PU operation and external operation (external/PU combined operation) and network operation (when RS-485 terminals or a communication option is used).

Pr.79

 

 

 

 

LED Indication

Description

 

 

 

:Off

Setting

 

 

 

 

 

 

 

 

:On

 

 

 

 

 

 

 

External/PU switchover mode ( Press

External operation

 

mode

 

 

0

 

 

 

 

 

 

to switch between the PU and

PU

EXT

NET

(initial

 

 

 

 

PU operation mode

value)

external operation mode.)

 

 

 

External operation mode at power-on

PU

EXT

NET

1

Fixed to PU operation mode

 

PU

EXT

NET

 

 

 

 

 

External operation

 

Fixed to external operation mode

 

mode

 

 

 

 

PU

EXT

NET

2

Operation can be performed by switching

NET operation

between the external and Net operation

 

 

mode.

 

 

 

mode

 

 

 

 

 

 

 

PU

EXT

NET

 

External/PU combined operation mode 1

 

 

 

 

Running frequency

Start signal

 

 

 

 

PU (FR-DU07 /

 

 

 

 

 

 

 

FR-PU04) setting

 

 

 

 

 

 

3

or external signal

External signal

 

 

 

 

input (multi-speed

input (terminal STF,

 

 

 

 

setting, across

 

 

 

 

STR)

 

 

 

 

 

 

terminals 4-5 (valid

 

 

 

 

 

 

 

 

 

 

 

 

 

when AU signal

 

 

 

PU

EXT

NET

 

turns on))

 

 

 

 

 

 

 

 

 

 

 

External/PU combined operation mode 2

 

 

 

 

Running frequency

Start signal

 

 

 

4

External signal

Input from the PU

 

 

 

(FR-DU07 / FR-

 

 

 

 

input (terminal 2, 4,

PU04)

 

 

 

 

 

1, Jog, multi-speed

 

 

 

 

 

 

 

 

 

 

 

 

setting, etc)

(

,

)

 

 

 

 

 

 

 

 

PU operation mode

 

 

 

 

 

PU

EXT

NET

 

Switch-over mode

 

 

 

External operation

 

 

 

 

mode

 

 

6

Switch among PU operation, external

 

 

 

 

 

operation, and NET operation while

PU

EXT

NET

 

 

keeping the same operation status.

NET operation

 

 

 

 

 

mode

 

 

 

 

 

 

 

PU

EXT

NET

 

External operation mode (PU operation

PU operation mode

 

interlock)

 

 

 

 

X12 signal ON

 

 

 

PU

EXT

NET

7

Operation mode can be switched to the

External operation

PU operation mode.

 

 

 

 

mode

 

 

 

(output stop during external operation)

 

 

 

 

 

 

 

X12 signal OFF

 

 

 

PU

EXT

NET

 

Operation mode can not be switched to

 

 

 

 

the PU operation mode.

 

 

 

 

 

￿Specify operation mode at power on (Pr.340)

When power is switched on or when power comes back on after instantaneous power failure, the inverter can be started up in the network operation mode.

After the inverter has started up in the network operation mode, parameter write and operation can be performed from a program. Set this mode for communication operation using the inverter RS- 485 terminals or communication option.

You can set the operation mode at power on (reset) according to the Pr. 79 and Pr. 340 settings.

Pr. 340

Pr.79

Operation mode at

Operation Mode

Power On, Power

Setting

Setting

Switchover

Restoration, Reset

 

 

 

0

 

 

 

(initial

As set in Pr. 79.

 

value)

 

 

 

 

0

NET operation mode

Can be switched to external,

 

PU or NET operation mode *2

 

 

 

 

1

PU operation mode

Fixed to PU operation mode

 

 

 

Can be switched to external

 

2

NET operation mode

or NET operation mode

 

Switching to PU operation

 

 

 

 

 

 

mode disabled

 

3, 4

External/PU combined

Operation mode switching

1, 2 *1

operation mode

disabled

 

 

6

NET operation mode

Can be switched to external,

 

PU or NET operation mode

 

 

 

with operation continued

 

 

X12 (MRS) signal ON

Can be switched to external,

 

 

.. NET operation mode

PU or NET operation mode *2

 

7

X12(MRS)signal OFF

Fixed to external operation

 

 

.. External operation

mode (Forcibly switched to

 

 

mode

external operation mode.)

 

0

NET operation mode

Can be switched to PU or

 

NET operation mode *3

 

 

 

 

1

PU operation mode

Fixed to PU operation mode

 

2

NEToperation mode

Fixed to NET operation mode

 

3, 4

External/PU combined

Operation mode switching is

10, 12

operation mode

disallowed

 

*1

6

NET operation mode

Can be switched to PU or

 

NET operation mode with

 

 

 

operation continued *3

 

7

External operation

Fixed to external operation

 

mode (Forcibly switched to

 

mode

 

 

external operation mode.)

 

 

 

*1 The Pr. 340 setting "2" or "12" is mainly used for communication operation using the inverter RS-485 terminals.

When a value other than "9999" (selection of automatic restart after instantaneous power failure) is set in Pr. 57 Restart coasting time, the inverter will resume the same operation state which was in before after power has been restored from an instantaneous power failure.

*2 The operation mode cannot be switched directly between the PU operation mode and network operation mode.

*3 Operation mode can be changed between the PU operation mode and

network operation mode with key of the operation panel (FR- DU07) and X65 signal.

Pr. Simple magnetic flux vector 80, 90 control

Pr.80 Motor capacity (simple magnetic flux vector control)

Pr.90 Motor constant (R1)

Providing optimum excitation to the motor can also produce high torque in a low-speed region. (simple magnetic flux vector control)

Set the used motor capacity (equal to or one rank higher than the inveter capacity) in Pr. 80.

The number of motor poles should be any of 2, 4 and 6 poles.

Single-motor operation (one motor for one inverter)

Wiring length from inverter to motor should be within 30m.

When simple magnetic flux vector control is not used, set "9999" (initial value) in Pr. 80.

For Pr. 90 Motor constant (R1), normally setting is not necessary. When you need more torque under simple magnetic flux vector control for other manufacturer's motor, set the motor primary resistance value (R1) for connection in Pr. 90

37

Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

Page 36