⋅The following gives the items which can be monitored by the cumulative saving power monitor (Pr. 52 = "51").
(The cumulative power monitor data digit can be shifted to the right by the number set in Pr. 891 Cumulative power monitor digit shifted times.)
Energy |
|
|
|
|
|
| |
Saving |
| Description and Formula |
|
| Increments | ||
Monitor |
|
|
| ||||
|
|
|
|
|
| ||
Item |
|
|
|
|
|
| |
Power | Power saving is added up per hour. |
|
| 0.01kWh/ | |||
saving |
|
| |||||
Σ (Power saving × ∆t) |
|
|
| 0.1kWh* | |||
amount |
|
|
| ||||
|
|
|
|
|
| ||
Power | Power saving amount represented in terms of |
| |||||
saving | 0.01/0.1* | ||||||
charge |
|
|
| ||||
amount |
|
|
| ||||
Power saving amount × Pr. 896 |
|
|
| ||||
charge |
|
|
| ||||
|
|
|
|
|
| ||
Annual | Estimated value of annual power saving amount |
| |||||
| Power saving amount |
| Pr.899 | 0.01kWh/ | |||
power |
| × 24 × 365 × | |||||
saving |
| Operation time during | 100 |
| 0.1kWh* | ||
amount |
| power saving totalization |
|
|
|
| |
|
|
|
|
|
|
| |
Annual | Annual power saving amount represented in |
| |||||
power | 0.01/0.1* | ||||||
saving | terms of charge |
|
|
| |||
amount | Annual power saving amount × Pr. 896 |
| |||||
charge |
|
|
|
|
|
|
*The increments vary according to the inverter capacity. (55K or less/75K or more)
Pr. C0(900), C1(901) | Adjustment of terminal FM |
and AM (calibration) | |
C0(Pr.900) FM terminal calibration | C1(Pr.901) AM terminal calibration |
The operation panel and parameter unit can be used to calibrate the full scales of the terminals FM and AM.
(1)FM terminal calibration (C0(Pr.900))
⋅The terminal FM is preset to output pulses. By setting the
Calibraton parameter C0 (Pr. 900), the meter connected to the inverter can be calibrated by parameter setting without use of a calibration resistor.
⋅Using the pulse train output of the terminal FM, a digital display can be provided by a digital counter. The monitor value is 1440 pulses/s output at the
Indicator |
|
|
|
1mA |
| (Digital indicator) | |
analog meter |
| ||
| |||
1mA |
| 1440 pulse/s(+) | |
FM | FM |
| |
(+) | T1 |
| |
Calibration |
|
|
|
resistor*1 |
| 8VDC |
|
|
|
|
SD | SD |
T2
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr. 55 (frequency monitor)
Set with Pr.56 (current monitor)
*1 Not needed when the operation panel
Used when calibration must be made near the frequency meter for such a reason as a remote frequency meter.
However, the frequency meter needle may not deflect to
(2)AM terminal calibration (C1(Pr.901))
⋅The AM terminal is
Pr. C2(902) to C7(905) Refer to the section about Pr. 125, Pr. 126
Pr. 989 Parameter for manufacturer setting. Do not set.
Pr. 990 Buzzer control of the operation panel
Pr.990 PU buzzer control
You can make the buzzer "beep" when you press key of the operation panel
Pr.990 Setting | Description |
0 | Without buzzer |
1(initial value) | With buzzer |
Pr. 991 PU contrast adjustment
Pr.991 PU contrast adjustment
Contrast adjustment of the LCD of the parameter unit (FR- PU04) can be performed.
Decreasing the setting value makes contrast light.
Pr.991 Setting | Description |
0 to 63 | 0 : Light |
↓ | |
| 63 : Dark |
Pr. 989, CL, ALLC, Er.CL, PCPY
Parameter clear, parameter copy
Pr.989 Parameter copy alarm release |
|
Pr.CL Parameter clear | ALLC All parameter clear |
Er.CL Alarm history clear | PCPY Parameter copy |
Set “1” in Pr.CL Parameter clear to initialize all parameters. (Calibration parameters are not cleared.)*
Set “1” in ALLC All parameter clear to initialize all parameters. *
Set “1” in Er.CL Alarm history clear to clear alarm history. *
Parameter settings can be copied to multiple inverters by using
PCPY.
When parameters are copied to the 75K or more inverter from
the 55K or less inverter or vice versa, an alarm appears on the operation panel.
For the parameters whose setting range differ, set Pr.989 as below after reset.
| 55K or less |
| 75K or more |
|
Pr.989 setting | 10 |
| 100 |
|
|
|
|
|
|
PCPY | Description |
|
| |
Setting |
|
| ||
|
|
|
|
0Cancel
1Copy the source parameters in the operation panel.
2Write the parameters copied to the operation panel to the destination inverter.
3Verify parameters in the inverter and operation panel.
*Parameters are not cleared when "1" is set in Pr.77 Parameter write selection.
|
| Features |
|
| |
|
|
| |||
|
|
| |||
Peripheral Devices | Why energy | savings? | |||
|
|
|
|
|
|
| Standard | Specifications |
| ||
|
|
|
|
|
|
Outline | Dimension | Drawings | |||
|
|
|
|
|
|
|
|
|
|
|
|
Terminal Connection | Diagram | Terminal Specification | Explanation | ||
|
|
|
|
|
|
| Operation | Panel |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| Parameter | List |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
Explanations | of | Parameters | |||
|
|
|
|
|
|
| Protective | Functions |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Options |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Instructions |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Motor |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Compatibility |
|
| |
|
|
|
|
|
|
|
| Warranty |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Inquiry |
|
| |
|
|
|
|
|
|
Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions. | 46 |