Pr. 52, 54, 158, 170, 171, 268, 563, 564, 867, 891
Change of DU/PU monitor descriptions Cumulative monitor clear
Pr.52 DU/PU main display data selection | Pr.54 FM terminal function selection |
Pr.158 AM terminal function selection | Pr.170 Cumulative power meter clear |
Pr.171 Operation hour meter clear | Pr.268 Monitor decimal digits selection |
Pr.563 Energization time | Pr.564 Operating time |
Pr.867 AM output filter |
|
Pr.891 Cumulative power monitor digit shifted times
The monitor to be displayed on the main screen of the operation panel
|
|
| Pr.52 Parameter |
| Pr.54 |
| |||
|
|
| Setting Value |
| (FM) | Full Scale | |||
Types of Monitor | Increments |
| DU |
|
| PU main |
| Pr.158 | Value |
|
|
|
|
|
| (AM) | |||
|
|
| LED |
| monitor |
|
| ||
|
|
|
|
| Setting |
| |||
Output frequency | 0.01Hz |
| 0/100 | 1 | Pr.55 | ||||
Output current | 0.01A/ |
| 0/100 | 2 | Pr.56 | ||||
0.1A*6 |
| ||||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| 200V |
Output voltage | 0.1V |
| 0/100 | 3 | class : 400V | ||||
| 400V | ||||||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| class : 800V |
Alarm display | |
| 0/100 |
| | | |||
Frequency setting | 0.01Hz | 5 |
|
| *1 | 5 | Pr.55 | ||
|
|
|
|
|
|
|
|
| Value of Pr. 55 |
Running speed | 1(r/min) | 6 |
|
| *1 | 6 | represented in | ||
|
| terms of Pr. 37 | |||||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| value |
Converter output |
|
|
|
|
|
|
|
| 200V |
0.1V | 8 |
|
| *1 | 8 | class : 400V | |||
voltage |
|
| 400V | ||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| class : 800V |
Regenerative brake |
|
|
|
|
|
|
|
| Brake duty set |
0.1% |
| 9 |
|
| *1 | 9 | in Pr. 30 and | ||
duty *5 |
|
|
| ||||||
|
|
|
|
|
|
|
| Pr. 70 | |
|
|
|
|
|
|
|
|
| |
Electronic thermal |
|
|
|
|
|
|
|
| Electronic |
|
|
|
|
|
|
|
| thermal relay | |
relay function load | 0.1% |
| 10 |
|
| *1 | 10 | ||
|
|
| function | ||||||
factor |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| operation level | |
|
|
|
|
|
|
|
|
| |
Output current peak | 0.01A/ | 11 |
|
| *1 | 11 | Pr.56 | ||
value | 0.1A*6 |
|
| ||||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| 200V |
Converter output | 0.1V | 12 |
|
| *1 | 12 | class : 400V | ||
voltage peak value |
|
| 400V | ||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| class : 800V |
Input power | 0.01kW/ | 13 |
|
| *1 | 13 | Rated inverter | ||
0.1kW*6 |
|
| power × 2 | ||||||
|
|
|
|
|
|
| |||
Output power | 0.01kW/ | 14 |
|
| *1 | 14 | Rated inverter | ||
0.1kW*6 |
|
| power × 2 | ||||||
|
|
|
|
|
|
| |||
Input terminal status | | 55 |
|
| *1 |
| | | |
Output terminal | |
|
| *1 |
| | | ||
status |
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |
Option input | | 56 |
|
| × |
| | | |
terminal status |
|
|
| ||||||
|
|
|
|
|
|
|
|
| |
Option output | | 57 |
|
| × |
| | | |
terminal status |
|
|
| ||||||
|
|
|
|
|
|
|
|
| |
Load meter | 0.1% |
|
|
| 17 | 17 | Pr.56 | ||
Reference voltage | | |
|
| | 21 | | ||
output |
|
| |||||||
|
|
|
|
|
|
|
|
| |
Cumulative | 1h |
|
| 20 |
| | | ||
energization time *2 |
|
|
| ||||||
|
|
|
|
|
|
|
|
| |
Actual operation | 1h |
|
| 23 |
| | | ||
time *2, 3 |
|
|
| ||||||
|
|
|
|
|
|
|
|
| |
Motor load factor | 0.1% |
|
|
| 24 | 24 | 200% |
*1 Selected by the parameter
*2 The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
When the operation panel
*3 The actual operation time is not added up if the cumulative operation time before power
*4 When using the parameter unit
*5 Setting can be made for the 75K or more.
*6 The setting depends on the inverter capacity.(55K or less/75K or more)⋅
⋅The cumulative power monitor value digit can be shifted to the right by the number set in Pr. 891.
⋅By setting “0” in Pr. 170, the cumulative power monitor can be cleared.
⋅You can check the numbers of cumulative energization time monitor exceeded 65535h with Pr. 563 and the numbers of actual operation time monitor exceeded 65535h with Pr. 564.
⋅Writing "0" in Pr. 171 clears the actual operation time monitor.
Pr. 268 Setting | Description |
9999 (initial value) | No function |
| When 1 or 2 decimal places (0.1 increments or 0.01 |
| increments) are monitored, the decimal places are |
0 | dropped and the monitor displays an integer value (1 |
| increments). |
| The monitor value of 0.99 or less is displayed as 0. |
| When 2 decimal places (0.01 increments) are |
| monitored, the 0.01 decimal place is dropped and the |
1 | monitor displays the first decimal place (0.1 |
increments). | |
| When the monitor display digit is originally in 1 |
| increments, it is displayed unchanged in 1 |
| increments. |
⋅When Pr. 52 is set to "100", the set frequency monitor is displayed during a stop and the output frequency monitor is displayed during operation. (LED of Hz flickers during stop and is lit during operation.)
|
| Pr.52 |
|
|
| 0 |
| 100 | |
| During | During stop |
| During |
| operation/stop |
| running | |
|
|
| ||
Output | Output frequency | Set frequency |
| Output frequency |
frequency |
| |||
|
|
|
| |
Output |
| Output current |
|
|
current |
|
|
| |
|
|
|
| |
Output |
| Output voltage |
|
|
voltage |
|
|
| |
|
|
|
| |
Alarm |
| Alarm display |
|
|
display |
|
|
| |
|
|
|
|
⋅Using Pr. 867 , the output voltage response of the terminal AM can be adjusted within the range 0 to 5s.
Pr. Change of the monitor output
55, 56 from terminal FM and AM
Pr.55 Frequency monitoring reference Pr.56 Current monitoring reference
Set the
Set the
|
| Features |
|
| |
|
|
| |||
|
|
| |||
Peripheral Devices | Why energy | savings? | |||
|
|
|
|
|
|
| Standard | Specifications |
| ||
|
|
|
|
|
|
Outline | Dimension | Drawings | |||
|
|
|
|
|
|
|
|
|
|
|
|
Terminal Connection | Diagram | Terminal Specification | Explanation | ||
|
|
|
|
|
|
| Operation | Panel |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| Parameter | List |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
Explanations | of | Parameters | |||
|
|
|
|
|
|
| Protective | Functions |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Options |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Instructions |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Motor |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Compatibility |
|
|
Cumulative power | 0.01kWh/ | 25 | | | |
0.1kWh *4, *6 | |||||
|
|
|
| ||
Power saving effect | Variable | 50 | 50 | Inverter | |
according | capacity | ||||
|
|
| |||
| to |
|
|
| |
Cumulative saving | 51 | | | ||
power | parameters | ||||
|
|
| |||
PID set point | 0.1% | 52 | 52 | 100% | |
PID measured value | 0.1% | 53 | 53 | 100% | |
PID deviation value | 0.1% | 54 | | |
Pulse speed(terminal FM)
2400 |
pulse/s |
1440 |
pulse/s |
Output frequency | Pr.55 | 400Hz |
reference |
|
|
Output current | Pr.56 | 500A |
reference |
|
|
Output voltage(terminal AM)
10VDC |
|
Pr.55 | 400Hz |
Pr.56 | 500A |
Warranty |
|
|
Inquiry |
|
Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions. | 32 |