Type

Terminal Symbol

Terminal Name

 

Description

 

 

 

 

 

Relay output 1 (alarm

Changeover contact output indicates that the inverter protective function has activated and the

 

Relay

A1, B1, C1

output stopped. Abnormal: No conduction across B-C (Across A-C Continuity), Normal: Across

 

output)

B-C Continuity (No conduction across A-C) Contact capacity: 230VAC 0.3A (Power factor=0.4)

 

 

 

 

 

 

 

30VDC 0.3A

 

 

 

 

 

 

 

 

 

 

 

A2, B2, C2

Relay output 2

1 changeover contact output Contact capacity: 230VAC 0.3A (Power factor=0.4) 30VDC 0.3A

 

 

 

RUN

Inverter running

Switched low when the inverter output frequency is equal to or

 

 

 

 

higher than the starting frequency (initial value 0.5Hz). Switched

 

 

 

 

 

 

high during stop or DC injection brake operation.*1

 

 

 

 

SU

Up to frequency

Switched low when the output frequency reaches within the range

Permissible load 24VDC

 

 

 

of ±10% (initial value) of the set frequency. Switched high during

0.1A

 

Open collector

 

 

 

acceleration/deceleration and at a stop.*1

(a voltage drop is 3.4V

 

 

 

 

Switched low when stall prevention is activated by the stall

maximum when the signal

circuitoutput signal

 

OL

Overload alarm

prevention function. Switched high when stall prevention is

is on)

 

 

 

cancelled. *1

 

Alarm code (4bit) output

 

IPF

Instantaneous power

Switched low when an instantaneous power failure and under

 

failure

voltage protections are activated. *1

(Refer to page 36)

 

 

 

FU

Frequency detection

Switched low when the inverter output frequency is equal to or

 

 

higher than the preset detected frequency and high when less than

 

 

 

 

the preset detected frequency. *1

 

Control

 

 

SE

Open collector output

Common terminal for terminals RUN, SU, OL, IPF, FU

 

 

 

common

 

 

 

 

 

 

 

 

 

 

 

 

 

Output item:

 

Pulse

 

 

 

 

 

Output frequency (initial

 

 

FM

For meter

 

 

setting)

 

 

 

 

Permissible load current

 

 

 

 

 

 

 

2mA

 

 

 

 

 

Select one e.g. output frequency from monitor items. *2

1440 pulses/s at 60Hz

 

 

 

 

 

Output item:

 

 

 

 

 

The output signal is proportional to the magnitude of the

 

 

 

 

 

Output frequency (initial

 

 

 

 

 

corresponding monitoring item.

 

 

 

 

 

setting)

 

Analog

 

 

 

 

 

 

 

AM

Analog signal output

 

 

Output signal 0 to 10VDC

 

 

 

 

Permissible load current

 

 

 

 

 

 

 

 

 

 

 

 

1mA (load impedance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10kΩ or more) Resolution

 

 

 

 

 

 

 

8 bit

 

 

 

 

 

With the PU connector, communication can be made through RS-485.

 

 

 

 

 

(for connection on a 1:1 basis only)

 

Communication

PU connector

PU connector

. Conforming standard

: EIA-485(RS-485)

 

. Transmission format

: Multidrop

 

 

 

 

 

 

 

 

. Communication speed

: 4800 to 38400bps

 

 

 

 

. Overall length

: 500m

 

 

TXD+

Inverter transmission

With the RS-485 terminal, communication can be made through RS-485.

RS-485

TXD-

terminal

Conforming standard

: EIA-485 (RS-485)

 

RXD+

Inverter reception

Transmission format

: Multidrop link

 

 

 

terminal

 

 

 

RXD-

terminal

Communication speed

: 300 to 38400bps

 

 

 

 

 

 

 

 

SG

Earth (Ground)

Overall length

: 500m

 

CAUTION

The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.

indicates that terminal functions can be selected fromPr. 178 to Pr. 196 (I/O terminal function selection)

*1. Low indicates that the open collector output transistor is on (conducts). High indicates that the transistor is off (does not conduct).

*2. Not output during inverter reset.

 

 

Features

 

 

 

 

 

 

 

 

Peripheral Devices

Why energy

savings?

 

 

 

 

 

 

 

Standard

Specifications

 

 

 

 

 

 

 

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification

Explanation

 

 

 

 

 

 

 

Operation

Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

List

 

 

 

 

 

 

 

 

 

 

 

 

 

Explanations

of

Parameters

 

 

 

 

 

 

 

Protective

Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compatibility

 

 

 

 

 

 

 

 

 

 

Warranty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 