Terminal Specification Explanation

Type

Terminal Symbol

Terminal Name

Description

 

 

 

R/L1, S/L2, T/L3

AC power input

Connect to the commercial power supply.

 

 

 

U, V, W

Inverter output

Connect a three-phase squirrel-cage motor.

 

 

 

R1/L11, S1/L21

Power supply for control

Connected to the AC power supply terminals R/L1 and S/L2. To retain the alarm display and

circuit

circuit

alarm output, apply external power to this terminal.

 

 

 

 

 

 

 

P/+, N/-

Brake unit connection

Connect the brake unit (FR-BU, BU, MT-BU5), power regeneration common converter (FR-

CV), power regeneration converter (MT-RC) or high power factor converter (FR-HC, MT-HC).

 

 

 

 

 

 

Main

 

 

 

 

 

 

P/+, P1

DC reactor connection

For the 55K or less, remove the jumper across terminals P/+ - P1 and connect the DC reactor.

(For the 75K or more, a DC reactor is supplied as standard.)

 

 

 

 

 

 

 

 

 

 

 

 

PR, PX

Please do not remove or use terminals PR and PX or the jumper connected.

 

 

 

 

 

 

 

 

Earth (Ground)

For earthing (grounding) the inverter chassis. Must be earthed (grounded).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STF

Forward rotation start

Turn on the STF signal to start forward rotation and turn it off to

When the STF and STR

 

 

stop.

signals are turned on

 

 

 

 

 

 

 

 

 

 

STR

Reverse rotation start

Turn on the STR signal to start reverse rotation and turn it off to

simultaneously, the stop

 

 

stop.

command is given.

 

 

 

 

 

 

 

 

 

 

STOP

Start self-holding

Turn on the STOP signal to self-hold the start signal.

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

RH, RM, RL

Multi-speed selection

Multi-speed can be selected according to the combination of RH, RM and RL signals.

 

 

JOG

Jog mode selection

Turn on the JOG signal to select Jog operation (initial setting) and turn on the start signal (STF

 

 

or STR) to start Jog operation.

 

 

 

 

 

 

 

 

 

 

 

 

RT

Second acceleration/

Turn on the RT signal to select second acceleration/deceleration time.

 

 

deceleration time

When the second function such as "second torque boost" and "second V/F (base frequency)"

 

 

 

 

 

 

 

selection

are set, turning on the RT signal selects these functions.

 

 

 

MRS

Output stop

Turn on the MRS signal (20ms or more) to stop the inverter output.

 

 

 

Use to shut off the inverter output when stopping the motor by electromagnetic brake.

 

input

 

 

 

 

 

 

 

 

 

 

 

 

 

Used to reset alarm output provided when protective function is activated. Turn on the RES

 

RES

Reset

signal for more than 0.1s, then turn it off.

 

 

Contact

 

 

 

 

 

 

Recover about 1s after reset is cancelled.

 

 

 

 

 

 

 

Terminal 4 input selection

Terminal 4 is made valid only when the AU signal is turned on. (The frequency setting signal

 

 

 

 

 

 

can be set between 4 and 20mADC.)

 

 

 

AU

 

Turning the AU signal on makes terminal 2 (voltage input) invalid.

 

 

 

 

 

 

 

 

PTC input

AU terminal is used as PTC input terminal (thermal protection of the motor). When using it as

 

 

 

 

 

 

 

PTC input terminal, set the AU/PTC switch to PTC.

 

signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selection of automatic

When the CS signal is left on, the inverter restarts automatically at power restoration. Note that

 

CS

restart after

input

 

instantaneous power

restart setting is necessary for this operation. In the initial setting, a restart is disabled.

 

 

 

 

 

 

 

 

 

 

 

 

failure

 

 

circuit

 

SD

Contact input common

Common terminal for contact input terminal (sink logic) and terminal FM. Common output

 

(sink)

terminal for 24VDC 0.1A power supply (PC terminal). Isolated from terminals 5 and SE.

 

 

 

 

 

 

Control

 

 

 

 

 

 

External transistor

When connecting the transistor output (open collector output), such as a programmable

 

 

 

 

 

 

common,

controller (PLC), when sink logic is selected, connect the external power supply common for

 

PC

24VDC power supply,

transistor output to this terminal to prevent a malfunction caused by undesirable currents. Can

 

 

 

 

 

 

 

contact input common

be used as 24VDC 0.1A power supply. When source logic has been selected, this terminal

 

 

 

 

 

 

 

(source)

serves as a contact input common.

 

 

 

10E

 

When connecting the frequency setting potentiometer at an initial

10VDC, permissible load

 

 

Frequency setting power

current 10mA.

 

 

 

 

 

 

 

status, connect it to terminal 10.

 

 

 

 

 

 

 

supply

5VDC, Permissible load

 

 

10

 

Change the input specifications when connecting it to terminal 10E.

 

 

 

 

 

 

 

 

 

current 10mA.

 

 

 

 

 

 

 

 

Inputting 0 to 5VDC (or 0 to 10V, 4 to 20mA) provides the maximum

output frequency at 5V

 

 

2

 

 

Frequency setting

(10V, 20mA) and makes input and output proportional. Use Pr.73 to switch from among input 0

 

 

 

 

to 5VDC (initial setting), 0 to 10VDC, and 4 to 20mA.

 

 

setting

 

 

(voltage)

 

 

 

 

 

 

 

Voltage input: Input resistance 10kΩ ± 1kΩ Maximum permissible voltage 20VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current input: Input resistance 250Ω ± 2% Maximum permissible current 30mA

 

Frequency

 

 

 

 

 

 

Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the maximum output frequency at 20mA

 

 

 

 

 

 

 

(5V, 10V) makes input and output proportional. This input signal is valid only when the AU

 

4

 

 

Frequency setting

signal is on (terminal 2 input is invalid). Use Pr.267 to switch between the input 4 to 20mA and 0

 

 

 

(current)

to 5VDC, 0 to 10VDC (initial setting).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage input: Input resistance 10kΩ ± 1kΩ Maximum permissible voltage 20VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current input: Input resistance 250Ω ± 2% Maximum permissible current 30mA

 

 

 

 

 

 

 

Frequency setting

Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal 2 or 4 frequency setting

 

 

1

 

 

signal. Use Pr.73 to switch between the input 0 to ±5VDC and 0 to ±10VDC (initial setting).

 

 

 

 

auxiliary

 

 

 

 

 

 

 

Input resistance 10kΩ ± 1kΩ, Maximum permissible voltage ± 20VDC

 

 

 

 

 

 

 

 

 

 

5

 

 

Frequency setting

Common terminal for frequency setting signal (terminal 2, 1 or 4) and analog output terminal

 

 

 

 

common

AM. Do not earth (ground).

 

 

 

 

 

 

 

 

 

17

Page 16
Image 16
Mitsubishi Electronics FR-F700 instruction manual Terminal Specification Explanation, Type, Terminal Name Description