Function | Parameters | Name |
| Setting Range | Increments | Initial Value | Refer to | |
| page | |||||||
|
|
|
|
|
|
| ||
| 66 | Stall prevention operation reduction | 0 to 400Hz | 0.01Hz | 60Hz | 30 | ||
| starting frequency | |||||||
|
|
|
|
|
|
| ||
Retry | 67 | Number of retries at alarm occurrence | 0 to 10, 101 to 110 | 1 | 0 | 34 | ||
68 | Retry waiting time | 0 to 10s | 0.1s | 1s | 34 | |||
| ||||||||
| 69 | Retry count display erase | 0 |
| 1 | 0 | 34 | |
| 70 | Special regenerative brake duty *2 | 0 to 10% | 0.1% | 0% | 31 | ||
| 71 | Applied motor | 0, 1, 2, 20 | 1 | 0 | 34 | ||
| 72 | PWM frequency selection | 0 to 15/0 to 6, 25*1 | 1 | 2 | 35 | ||
| 73 | Analog input selection | 0 to 7, 10 to 17 | 1 | 1 | 35 | ||
| 74 | Input filter time constant | 0 to | 8 | 1 | 1 | 36 | |
| 75 | Reset selection/disconnected PU | 0 to 3, 14 to 17 | 1 | 14 | 36 | ||
| detection/PU stop selection | |||||||
|
|
|
|
|
|
| ||
| 76 | Alarm code output selection | 0, 1, | 2 | 1 | 0 | 36 | |
| 77 | Parameter write selection | 0, 1, | 2 | 1 | 0 | 36 | |
| 78 | Reverse rotation prevention selection | 0, 1, | 2 | 1 | 0 | 36 | |
| 79 | Operation mode selection | 0, 1, 2, 3, 4, 6, 7 | 1 | 0 | 37 | ||
Simple fluxmagnetic controlvector | 80 | Motor capacity (simple magnetic flux | 0.4 to 55kW, 9999 | 0.01/0.1kW*1 | 9999 | 37 | ||
vector control) | /0 to 3600kW, 9999*1 | |||||||
| ||||||||
|
|
|
|
| ||||
| 90 | Motor constant (R1) | 0 to 50Ω, 9999 | 0.001Ω/ | 9999 | 37 | ||
| /0 to 400mΩ, 9999*1 | 0.01mΩ*1 | ||||||
|
|
|
|
| ||||
|
|
|
|
|
|
| ||
| 100 | V/F1 (first frequency) | 0 to 400Hz, 9999 | 0.01Hz | 9999 | 38 | ||
V/F | 101 | V/F1 (first frequency voltage) | 0 to 1000V | 0.1V | 0V | 38 | ||
102 | V/F2 (second frequency) | 0 to 400Hz, 9999 | 0.01Hz | 9999 | 38 | |||
points | ||||||||
103 | V/F2 (second frequency voltage) | 0 to 1000V | 0.1V | 0V | 38 | |||
| ||||||||
5 | 104 | V/F3 (third frequency) | 0 to 400Hz, 9999 | 0.01Hz | 9999 | 38 | ||
Adjustable | 105 | V/F3 (third frequency voltage) | 0 to 1000V | 0.1V | 0V | 38 | ||
106 | V/F4 (fourth frequency) | 0 to 400Hz, 9999 | 0.01Hz | 9999 | 38 | |||
| ||||||||
| 107 | V/F4 (fourth frequency voltage) | 0 to 1000V | 0.1V | 0V | 38 | ||
| 108 | V/F5 (fifth frequency) | 0 to 400Hz, 9999 | 0.01Hz | 9999 | 38 | ||
| 109 | V/F5 (fifth frequency voltage) | 0 to 1000V | 0.1V | 0V | 38 | ||
| 117 | PU communication station | 0 to 31 | 1 | 0 | 38 | ||
connectorPU communication | 118 | PU communication speed | 48, 96, 192, 384 | 1 | 192 | 38 | ||
123 | PU communication waiting time setting | 0 to 150ms, 9999 | 1 | 9999 | 38 | |||
| 119 | PU communication stop bit length. | 0, 1, 10, 11 | 1 | 1 | 38 | ||
| 120 | PU communication parity check | 0, 1, 2 | 1 | 2 | 38 | ||
| 121 | Number of PU communication retries | 0 to 10, 9999 | 1 | 1 | 38 | ||
| 122 | PU communication check time interval | 0, 0.1 to 999.8s, 9999 | 0.1s | 9999 | 38 | ||
|
|
|
|
|
|
|
| |
| 124 | PU communication CR/LF presence/ | 0, 1, 2 | 1 | 1 | 38 | ||
| absence selection | |||||||
|
|
|
|
|
|
| ||
| 125 | Terminal 2 frequency setting gain | 0 to 400Hz | 0.01Hz | 60Hz | 39 | ||
| frequency | |||||||
|
|
|
|
|
|
| ||
| 126 | Terminal 4 frequency setting gain | 0 to 400Hz | 0.01Hz | 60Hz | 39 | ||
| frequency | |||||||
|
|
|
|
|
|
| ||
| 127 | PID control automatic switchover | 0 to 400Hz, 9999 | 0.01Hz | 9999 | 39 | ||
| freqeuncy | |||||||
|
|
|
|
|
|
| ||
operation | 128 | PID action selection | 10, 11, 20, 21, 50, 51, 60, | 1 | 10 | 39 | ||
61 |
| |||||||
|
|
|
|
|
| |||
129 | PID proportional band | 0.1 to 1000%, 9999 | 0.1% | 100% | 39 | |||
| ||||||||
| 130 | PID integral time | 0.1 to 3600s, 9999 | 0.1s | 1s | 39 | ||
PID | 131 | PID upper limit | 0 to 100%, 9999 | 0.1% | 9999 | 39 | ||
132 | PID lower limit | 0 to 100%, , 9999 | 0.1% | 9999 | 39 | |||
| ||||||||
| 133 | PID action set point | 0 to 100%, 9999 | 0.01% | 9999 | 39 | ||
| 134 | PID differential time | 0.01 to 10.00s, 9999 | 0.01s | 9999 | 39 |
*1 Differ according to capacities. (55K or less/75K or more) *2 Setting can be made for the 75K or more.
23