Name (type)

Specifications, Structure, etc.

￿The brake unit and resistor unit are options that will fully exhibit the regenerative braking capability of the inverter and are always used as a set.

￿There are six different brake units as in the following table, from which make selection according to the necessary braking torque and deceleration time.

￿The brake unit is equipped with a seven-segment LED that displays the duty (%ED) and alarm.

￿Brake unit selection table

￿%ED at short-time rating when braking torque is 100%

 

 

Motor Capacity

5.5kW

7.5kW

11kW

15kW

18.5kW

22kW

30kW

37kW

45kW

55kW

 

 

Inverter

200V

5.5K

7.5K

11K

15K

18.5K

22K

30K

37K

45KK

55K

 

 

400V

5.5K

7.5K

11K

15K

18.5K

22K

30K

37K

45KK

55K

 

 

 

 

2

FR-BU-15K

 

80

40

15

10

------

------

------

------

------

------

unit

0

FR-BU-30K

%ED

------

------

65

30

25

15

10

------

------

------

 

0

 

 

 

 

 

 

 

 

 

 

 

 

Brake

V

FR-BU-55K

 

------

------

------

------

90

60

30

20

15

10

0

FR-BU-H30K

%ED

80------

------

65

30

25

15

10

------------

------

------

 

4

FR-BU-H15K

 

40

15

10

------

------

------

------

------

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

V

FR-BU-H55K

 

------

------

------

------

90

60

30

20

15

10

￿Braking torque (%) at short-time rating when 10%ED is 15s

 

 

Motor Capacity

5.5kW

7.5kW

11kW

15kW

18.5kW

22kW

30kW

37kW

45kW

55kW

 

 

 

Inverter

200V

5.5K

7.5K

11K

15K

18.5K

22K

30K

37K

45KK

55K

 

 

 

400V

5.5K

7.5K

11K

15K

18.5K

22K

30K

37K

45KK

55K

 

 

 

 

 

 

2

FR-BU-15K

Braking

280

200

120

100

80

70

------

------

------

------

 

unit

0

FR-BU-30K

Torque

------

------

260

180

160

130

100

80

70

------

Brake unit

V

FR-BU-55K

(%)

------

------

------

------

300

250

180

150

120

100

Brake

0

 

 

 

 

 

 

 

 

 

 

 

 

Resistor unit

0

FR-BU-H30K

Torque

------

------

260

180

160

130

100

80

70

------

 

 

4

FR-BU-H15K

Braking

280

200

120

100

80

70

------

------

------

------

 

 

0

 

(%)

 

 

 

 

 

 

 

 

 

 

 

 

V

FR-BU-H55K

------

------

------

------

300

250

180

150

120

100

 

Brake unit

￿ Brake unit and resistor unit combinations and used cables

 

 

 

 

 

 

(Note) 1. The temperature rise of the resistor unit is about a

 

 

Brake Unit Type

Resistor Unit Type

Cable (P/+-P/+, N/--

FR-BU-(H)￿￿K

 

 

maximum of 100°C. Therefore, use heat-resistant wires

 

 

 

 

N/-, P/+-P, PR-PR)

Resistor unit

 

2

FR-BU-15K

FR-BR-15K

3.5mm2

(such as glass wires).

 

 

FR-BR-(H)￿￿K

 

0

FR-BU-30K

FR-BR-30K

5.5mm2

 

 

0

 

 

 

V

FR-BU-55K

FR-BR-55K

14mm2

 

 

 

4

FR-BU-H15K

FR-BR-H15K

3.5mm2

 

 

 

0

FR-BU-H30K

FR-BR-H30K

3.5mm2

 

 

 

0

FR-BU-H55K

FR-BR-H55K

5.5mm2

 

 

 

V

 

Use the wires of the above recommended size or larger.

￿ Connection example

 

 

 

 

 

 

*3

 

 

 

 

 

 

 

 

 

ON

Inverter

 

 

 

 

 

 

 

 

 

 

FR-BU

FR-BR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

P/+

P/+

P/+

P

 

 

 

T *2

 

 

 

 

 

 

 

 

MC

 

 

 

 

 

 

 

 

 

 

N/-

N/-

PR

PR

 

 

 

 

 

 

 

 

 

 

 

MC

 

 

 

 

 

 

 

 

 

 

 

FR-BR

Within

 

Within

 

 

 

 

 

 

5m

 

5m

 

MCCB

MC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R/L1

U

Motor

P

TH1

Inverter

 

 

 

 

 

 

 

 

 

Three-phase AC

 

 

 

 

 

 

 

 

S/L2

V

IM

 

 

 

 

FR-BU

FR-BR

power supply

 

PR

 

 

 

 

 

 

 

 

Twist

 

 

Twist

 

 

T/L3

W

 

 

TH2

 

 

 

 

 

 

P/+

 

P/+ P/+

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter

 

FR-BU

N/-

 

N/- PR

PR

 

 

 

 

 

PR

HA

 

 

 

 

 

 

 

 

 

 

Within 10m

 

Within 10m

 

 

 

 

 

 

 

 

 

 

 

P/+

*1

P/+

HB

 

 

 

 

 

 

 

N/

N/

HC

 

 

 

 

 

 

 

 

*3. Minimize the cable length between the inverter and brake

 

 

 

 

*3

 

 

unit and the resistor unit and brake unit. Use a twisted

 

 

 

 

 

 

cable when the wiring length exceeds 5m. (If twisted

 

 

 

 

5m or less

 

 

 

 

 

 

 

 

wires are used, the distance should be within 10m.) Use

*1. Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU (H)) terminals so that their

the wires of the above recommended size or larger.

terminal signals match with each other.

 

 

 

 

 

 

 

 

 

(Incorrect connection will damage the inverter.)

 

 

 

 

 

 

 

 

*2. When the power supply is 400V class, install a step-down transformer.

 

 

 

 

 

 