Function

Parameters

Name

Setting Range

Increments

Initial Value

Refer to

page

 

 

 

 

 

 

867

AM output filter

0 to 5s

0.01s

0.01s

32

872

Input phase failure protection selection

0, 1

1

0

42

Regeneration functionavoidance

882

Regeneration avoidance operation

0, 1

1

0

45

selection

 

 

 

 

 

883

Regeneration avoidance operation level

300 to 800V

0.1V

380V/760V*1

45

 

 

884

Regeneration avoidance at deceleration

0 to 5

1

0

45

 

detection sensitivity

 

 

 

 

 

 

 

885

Regeneration avoidance compensation

0 to 10Hz, 9999

0.01Hz

6Hz

45

 

frequency limit value

 

 

 

 

 

 

 

886

Regeneration avoidance voltage gain

0 to 200%

0.1%

100%

45

Free parameter

888

Free parameter 1

0 to 9999

1

9999

45

889

Free parameter 2

0 to 9999

1

9999

45

 

 

 

 

 

 

 

 

 

891

Cumulative power monitor digit shifted

0 to 4, 9999

1

9999

32

 

times

 

 

 

 

 

 

monitor

892

Load factor

30 to 150%

0.1%

100%

45

893

Energy saving monitor reference (motor

0.1 to 55/0 to 3600kW*2

0.01/0.1kW*2

Inverter rated

45

 

 

capacity)

capacity

 

 

 

 

 

saving

894

Control selection during commercial

0, 1, 2, 3

1

0

45

power-supply operation

 

 

 

 

 

 

 

Energy

895

Power saving rate reference value

0, 1, 9999

1

9999

45

897

Power saving monitor average time

0, 1 to 1000h, 9999

1

9999

45

 

896

Power unit cost

0 to 500, 9999

0.01

9999

45

 

 

 

 

 

 

 

 

898

Power saving cumulative monitor clear

0, 1, 10, 9999

1

9999

45

 

899

Operation time rate (estimated value)

0 to 100%, 9999

0.1%

9999

45

 

C0

FM terminal calibration

 

 

 

46

 

(900)

 

 

 

 

 

 

 

C1

AM terminal calibration

 

 

 

46

 

(901)

 

 

 

 

 

 

 

C2

Terminal 2 frequency setting bias

0 to 400Hz

0.01Hz

0Hz

39

 

(902)

frequency

 

 

 

 

 

parameters

C3

Terminal 2 frequency setting bias

0 to 300%

0.1%

0%

39

(902)

 

 

 

 

 

 

 

 

125

Terminal 2 frequency setting gain

0 to 400Hz

0.01Hz

60Hz

39

 

(903)

frequency

 

 

 

 

 

Calibration

C4

frequency

0 to 300%

0.1%

100%

39

(904)

 

(903)

Terminal 2 frequency setting gain

 

C5

Terminal 4 frequency setting bias

0 to 400Hz

0.01Hz

0Hz

39

 

 

 

 

 

 

 

 

 

 

 

C6

Terminal 4 frequency setting bias

0 to 300%

0.1%

20%

39

 

(904)

 

 

 

 

 

 

 

126

Terminal 4 frequency setting gain

0 to 400Hz

0.01Hz

60Hz

39

 

(905)

frequency

 

 

 

 

 

 

C7

Terminal 4 frequency setting gain

0 to 300%

0.1%

100%

39

 

(905)

 

 

 

 

 

 

989

Parameter copy alarm release

10/100

1

10/100*2

-

PU

990

PU buzzer control

0, 1

1

1

46

￿ 991

PU contrast adjustment

0 to 63

1

58

46

 

Clear parameters

Pr.CL

Parameter clear

0, 1

1

0

46

PCPY

Parameter copy

0, 1, 2, 3

1

0

46

 

ALLC

All parameter clear

0, 1

1

0

46

 

Er.CL

Alarm history clear

0, 1

1

0

46

 

 

 

 

 

 

 

*1 The initial value differs according to the voltage class. (200V class / 400V class) *2 Differ according to capacities. (55K or less/75K or more)

27

Page 26
Image 26
Mitsubishi Electronics FR-F700 867, 872, 882, 883, 884, 885, 886, 888, 889, 891, 892, 893, 894, 895, 897, 896, 898, 899