Mitsubishi Electronics FR-F700 Common specifications, Can be selected, Operating status

Models: FR-F700

1 65
Download 65 pages 14.03 Kb
Page 7
Image 7

Common specifications

 

Control system

 

High carrier frequency PWM control (V/F control)/optimum excitation control/simple magnetic flux vector control

 

Output frequency range

0.5 to 400Hz

 

 

 

 

 

0.015Hz/0 to 60Hz (terminal 2, 4: 0 to 10V/12bit)

 

Frequency

 

Analog input

0.03Hz/0 to 60Hz (terminal 2, 4: 0 to 5V/11bit, 0 to 20mA/11bit, terminal 1: -10V to +10V/11bit)

specifications

setting resolution

 

 

0.06Hz/0 to 60Hz (terminal 1: 0 to ±5V/10bit)

 

 

 

Digital input

0.01Hz

 

Frequency

 

Analog input

Within ±0.2% of the max. output frequency (25°C ± 10°C)

 

accuracy

 

Digital input

Within 0.01% of the set output frequency

Control

Voltage/frequency characteristics

Base frequency can be set from 0 to 400Hz Constant torque/variable torque pattern or adjustable 5 points V/F can

120% (3Hz) when set to simple magnetic flux vector control and slip compensation

Starting torque

 

 

 

 

 

 

be selected

 

 

 

 

 

 

 

Acceleration/deceleration time setting

0 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode

 

can be selected.

 

 

 

 

 

 

DC injection brake

 

Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) variable

 

Stall prevention operation level

Operation current level can be set (0 to 150% adjustable), whether to use the function or not can be selected

 

Frequency

 

Analog input

Terminal 2, 4: 0 to 10V, 0 to 5V, 4 to 20mA can be selected

 

 

Terminal 1: -10 to +10V, -5 to 5V can be selected

 

setting signal

 

 

 

 

Digital input

Four-digit BCD or16-bit binary using the setting dial of the operation panel (when used with the option FR-A7AX)

 

 

 

 

 

Start signal

 

Available individually for forward rotation and reverse rotation. Start signal automatic self-holding input (3-wire input)

 

 

can be selected.

 

 

 

 

 

 

 

 

 

 

You can select any twelve signals using Pr.178 to Pr.189 (input terminal function selection) from among multi speed

 

 

 

 

 

selection, second function selection, terminal 4 input selection, JOG operation selection, selection of automatic

 

Input signals

 

restart after instantaneous power failure, external thermal relay input, HC connection (inverter operation enable

 

 

signal), HC connection (instantaneous power failure detection), PU operation/external inter lock signal , PID control

 

 

 

 

 

enable terminal, PU operation, external operation switchover, output stop, start self-holding selection, forward

 

 

 

 

 

rotation command, reverse rotation command, inverter reset, PTC thermistor input, PID forward reverse operation

 

 

 

 

 

switchover, PU-NET operation switchover, NET-external operation switchover, command source switchover.

specifications

 

 

 

 

Maximum and minimum frequency settings, frequency jump operation, external thermal relay input selection, polarity

Operational functions

reversible operation, automatic restart after instantaneous power failure operation, original operation continuation at

 

 

instantaneous power failure, commercial power supply-inverter switchover operation, forward/reverse rotation

 

 

 

 

 

 

 

 

 

 

prevention, operation mode selection, PID control, computer link operation (RS-485).

 

 

 

 

 

You can select any seven signals using Pr.190 to Pr.196 (output terminal function selection) from among inverter

Operation

 

Operating status

running, up-to-speed, instantaneous power failure /undervoltage, overload warning, output frequency detection, second

 

inverter switchover MC2, commercial power supply-inverter switchover MC3, fan fault output, heatsink overheat pre-

 

 

 

 

 

output frequency detection, regenerative brake prealarm*4, electronic thermal relay function pre-alarm, PU operation

 

 

 

 

 

mode, inverter operation ready, output current detection, zero current detection, PID lower limit, PID upper limit, PID

 

 

 

 

 

forward rotation reverse rotation output, commercial power supply-inverter switchover MC1, commercial power supply-

 

signals

 

 

 

alarm, inverter running start command on, deceleration at an instantaneous power failure, PID control activated, during

 

 

 

 

retry, during PID output suspension, life alarm, alarm output 3 (power-off signal), power savings average value update

 

 

 

 

output. Open collector output (5 points), relay output (2 points) and alarm code of the inverter can be output (4 bit) from

 

 

 

 

 

timing, current average monitor, alarm output 2, maintenance timer alarm, remote output, minor failure output, alarm

 

Output

 

 

 

the open collector.

 

 

 

When used with the

You can select any seven signals using Pr.313 to Pr. 319 (extension output terminal function selection) from among

 

 

 

 

FR-A7AY, FR-A7AR

control circuit capacitor life, main circuit capacitor life, cooling fan life, inrush current limit circuit life and the above

 

 

 

 

(option)

stated signals. (Only positive logic can be set for terminals of the FR-A7AR.)

 

 

 

 

 

Selection can be made from output frequency, motor current (steady or peak value), output voltage, frequency setting

 

 

 

 

 

value, running speed, converter output voltage (steady or peak value), electronic thermal relay function load factor,

 

 

Pulse/analog output

input power, output power, load meter, reference voltage output, motor load factor, power saving effect, regenerative

 

 

 

 

 

brake duty*4, PID set value, PID measured value using Pr.54 "FM terminal function selection (pulse train output)" and

 

 

 

 

 

Pr.158 "AM terminal function selection (analog output)".

 

 

 

 

 

Output frequency, motor current (steady or peak value), output voltage, frequency setting, running speed, converter

 

 

 

 

 

output voltage (steady or peak value), electronic thermal relay function load factor, input power, output power, load

 

 

 

 

Operating status

meter, cumulative energization time, actual operation time, motor load factor, cumulative energization power, power

Display

PU

 

saving effect, cumulative saving power, regenerative brake duty*4, PID set point, PID measured value, PID deviation

 

 

 

 

status monitor*2, terminal assignment status*2

FR-PU04)

 

 

 

(FR-DU07/

 

 

value, inverter I/O terminal monitor, input terminal option monitor*1, output terminal option monitor*1, option fitting

 

 

 

 

 

 

 

 

Alarm definition

Alarm definition is displayed when the protective function is activated, the output voltage/current/frequency/cumulative

 

 

 

 

energization time right before the protection function was activated and the past 8 alarm definitions are stored

 

 

 

 

 

 

 

 

 

Interactive guidance

Operation guide/trouble shooting with a help function*2

 

 

 

 

 

Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage

 

 

 

 

 

during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal

 

 

 

 

 

operation, motor protection thermal operation, heatsink overheat, instantaneous power failure occurrence,

 

 

 

 

 

undervoltage, input phase failure, motor overload, output side earth (ground) fault overcurrent, output phase failure,

Protective/warning function

external thermal relay operation, PTC thermistor operation, option alarm, parameter error, PU disconnection, retry

count excess, CPU alarm, operation panel power supply short circuit, 24VDC power output short circuit, output

 

 

 

 

 

 

 

 

 

 

current detection value excess, inrush resistance overheat, communication alarm (inverter), analog input alarm,

 

 

 

 

 

internal circuit alarm (15V power supply), fan fault, overcurrent stall prevention, overvoltage stall prevention,

 

 

 

 

 

electronic thermal relay function prealarm, PU stop, maintenance timer alarm*1, brake transistor alarm*4, parameter

 

 

 

 

 

write error, copy operation error, operation panel lock, parameter copy alarm

Environment

Ambient temperature

-10°C to +50°C (non-freezing)

Ambient humidity

 

90%RH or less (non-condensing)

 

Storage temperature*3

-20°C to +65°C

 

Atmosphere

 

Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)

 

Altitude, vibration

 

Maximum 1000m above seal level, 5.9m/s2 or less *5 (conforms to JIS C 60068-2-6)

*1. Can be displayed only on the operation panel (FR-DU07).

*2. Can be displayed only on the parameter unit (FR-PU04).

*3. Temperature applicable for a short period in transit, etc.

*4. Only the 75K or more functions.

*5. 2.9m/s2 or less for the 185K or more.

 

 

Features

 

 

 

 

 

 

 

 

Peripheral Devices

Why energy

savings?

 

 

 

 

 

 

 

Standard

Specifications

 

 

 

 

 

 

 

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification