Section 7, Plumbing the System

NOTICE

Figure 7-1 Heating Module

All fittings, hose and/or tubing involving the domestic water component of the Distribution Module, must be approved for use with domestic water and rated for the domestic water system pressure

All plumbing lines must be run and secured so as to prevent damage, chafing and kinking

Ensure that the coolant flow is adequate through the Oasis™ Heating Module and the system. An indication of inadequate flow is, when the Oasis™ Heating Module is running and up to normal operating temperature, the difference between the inlet and outlet coolant temperature to the Oasis™ Heating Module is less than 20F.

The Distribution Module contains three distribution pumps and one heat exchanger and is pre-wired and pre-plumbed for ease of installation.

The Heating and Distribution Modules should be filled and flushed prior to operation to remove any foreign debris.