Section 9, Installing the Distribution Module
9.7Distribution Module Zone Control Board
The Zone Control Board has four
•10 pin connector to Heating Module Remote Operating Panel.
•8 pin connector to Heating Module (connector cord transitions to a 9 pin connector for the Heating Module).
•12 pin connector to Distribution Module (connector cord transitions to a 9 pin connector for the Distribution Module).
•14 pin connector to thermostat and cabin fan connector plug.
Cabin Fan leads•The positive (red) lead from each cabin fan is to be attached to one of the trailing cabin fan leads, color coded for zones, from the thermostat and cabin fan connector plug.
•The negative lead from each cabin fan is to be attached to a ground terminal (not provided) that is connected to a battery ground.
•The cabin fan 1 leads (orange) can supply up to a maximum of 10 Amps. The other cabin fan leads
•If the system requires higher amperage draws, install a separate relay to power the fans. This relay will use the existing fan circuit as a signal and must be wired to a secondary power source (not the heater’s control board). See Figure