UPS Only Installation
NOTE Input neutral must be wired for proper operation.
Table 2. UPS Terminal Block WiringWire Function | Terminal | Minimum | Tightening | Conduit Connection |
| |
Position | Wire Size* | Torque | (Entry Size) |
| ||
|
|
| ||||
Input | Ground | 8 AWG |
|
|
| |
|
|
|
|
|
|
|
| L1 | 3 AWG | 25 lb in | 2” access hole for | ||
|
|
|
| |||
| Neutral | 3 AWG | (2.83 Nm) | |||
|
|
|
|
|
|
|
| L2 | 3 AWG |
|
|
| |
|
|
|
|
|
|
|
Output | L1 | 3 AWG |
|
|
| |
|
|
|
|
|
|
|
| Neutral | 3 AWG | 25 lb in | 2” access hole for | ||
|
|
|
| |||
| L2 | 3 AWG | (2.83 Nm) | |||
|
|
|
|
|
|
|
| Ground | 8 AWG |
|
|
|
*Use only
TB1 | 1 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
|
| 2 |
|
|
|
|
|
|
InputOutput
Figure 6. UPS Terminal Block
8.Replace the UPS wiring access cover.9.Continue to “Stabilizing the Cabinet” on page 49 to complete the UPS installation.