UPS Maintenance
Using the UPS-Mounted Maintenance Bypass Switch
The
Figure 41. Maintenance Bypass Switch (PDM Shown)
|
| The |
|
|
|
| Table 14. |
|
|
|
|
|
|
|
|
| NOTE In the UPS or SERVICE position, AC input power is still |
|
|
|
| connected to the input terminals inside the UPS. |
|
|
Table 14. |
|
| ||
Switch Position |
| Description |
|
|
UPS | Connects the UPS output to the load. |
|
| |
|
|
|
| |
SERVICE | Connects the load directly to AC input power and disconnects UPS output. AC input |
|
| |
| power is still connected to the UPS input. |
|
| |
BYPASS | Like the SERVICE position, BYPASS connects the load directly to AC input power and |
|
| |
| disconnects UPS output. However, because BYPASS also disconnects AC input |
|
| |
| from the UPS, this is the appropriate position for UPS maintenance or repair. |
| ||
Powerware® 9155 UPS | 79 |
|