Operation

Table 13. User Settings (continued)

Description

Available Settings

Default Setting

Site Wiring Fault Notice

Enabled/Disabled

Enabled

 

 

 

Reset Custom Event Settings

0 through 32

Empty

 

 

 

Full Power Battery Test

Enabled/Disabled

Enabled

 

 

 

Auto Output Configuration

Enabled/Disabled

Enabled for initial startup

 

 

Disabled after initial startup

 

 

 

UPS Startup

W A R N I N G

Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.

Verify that UPS installation has been carried out correctly and the UPS ground has been connected.

Maintenance Bypass Startup

If you have an optional Maintenance Bypass Module or Power Distribution Module, you can start up the UPS in maintenance bypass, allowing utility power to supply the load.

To start up the UPS in maintenance bypass:

1.Verify that the Maintenance Bypass switch is in the BYPASS position (see Figure 41 on page 79).

2.Switch on utility power where the UPS is connected. The load is now powered by utility power.