Operation
Table 13. User Settings (continued)
Description | Available Settings | Default Setting |
Site Wiring Fault Notice | Enabled/Disabled | Enabled |
|
|
|
Reset Custom Event Settings | 0 through 32 | Empty |
|
|
|
Full Power Battery Test | Enabled/Disabled | Enabled |
|
|
|
Auto Output Configuration | Enabled/Disabled | Enabled for initial startup |
|
| Disabled after initial startup |
|
|
|
UPS Startup
W A R N I N G
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.
Verify that UPS installation has been carried out correctly and the UPS ground has been connected.
Maintenance Bypass Startup
If you have an optional Maintenance Bypass Module or Power Distribution Module, you can start up the UPS in maintenance bypass, allowing utility power to supply the load.
To start up the UPS in maintenance bypass:
1.Verify that the Maintenance Bypass switch is in the BYPASS position (see Figure 41 on page 79).
2.Switch on utility power where the UPS is connected. The load is now powered by utility power.
70 | Powerware® 9155 UPS |