Specifications
Table 17. Dimensions and Weights
| Dimensions (H x W x D) | Weight |
|
32.2” × 12” × 32” (81 × 30 × 81 cm) | 352 lb (160 kg) | ||
47.8” × 12” × 32” (121.5 × 30 × 81 cm) | 550 lb (250 kg) | ||
47.8” × 12” × 32” (121.5 × 30 × 81 cm) | 590 lb (268 kg) | ||
32.2” × 12” × 30.3” (81 × 30 × 77 cm) | 480 lb (218 kg) | ||
47.8” × 12” × 30.3” (121.5 × 30 × 77 cm) | 710 lb (322 kg) | ||
PDM (rear UPS mount) | 16.5” × 12” × 7” (42 × 30 × 17.8 cm) | 25 lb (11 kg) | |
MBM (rear UPS mount) | 16.5” × 12” × 7” (42 × 30 × 17.8 cm) | 18 lb (8 kg) |
Operating Temperature | 10°C to 40°C (50°F to 104°F) |
| Optimal battery performance: 25°C (77°F) |
Transit Temperature | |
Storage Temperature | 0°C to 25°C (32°F to 77°F) |
| Recommended battery storage: 59°F (15°C) to 77°F (25°C) |
Ventilation | Front air intake, forced air, two fans, positive pressurization, |
| temperature |
Altitude | 9,843 ft (3,000m) operating without derating |
| 32,810 ft (10,000m) during transportation |
Relative Humidity | |
Heat Dissipation | 5582 BTU/hr maximum online |
| 5294 BTU/hr maximum on battery |
Audible Noise | <56 dBA at 1 meter distance, typical loads |
| <62 dBA for heavy load, high ambient or high altitude, on battery |
Safety Conformance | |
| EN 55022 Class A (CISPR22 Class A) and IEC 60950; IEC |
Agency Markings | UL, cUL, CE, |
EMC (Class A) | IEC |
Surges | IEEE/ANSI C62.41 Cat B3 |
|
|
86 | Powerware® 9155 UPS |