Specifications

Table 17. Dimensions and Weights

 

Dimensions (H x W x D)

Weight

 

2-High UPS

32.2” × 12” × 32” (81 × 30 × 81 cm)

352 lb (160 kg)

3-High UPS-32

47.8” × 12” × 32” (121.5 × 30 × 81 cm)

550 lb (250 kg)

3-High UPS-64

47.8” × 12” × 32” (121.5 × 30 × 81 cm)

590 lb (268 kg)

2-High EBM

32.2” × 12” × 30.3” (81 × 30 × 77 cm)

480 lb (218 kg)

3-High EBM

47.8” × 12” × 30.3” (121.5 × 30 × 77 cm)

710 lb (322 kg)

PDM (rear UPS mount)

16.5” × 12” × 7” (42 × 30 × 17.8 cm)

25 lb (11 kg)

MBM (rear UPS mount)

16.5” × 12” × 7” (42 × 30 × 17.8 cm)

18 lb (8 kg)

Table 18. Environmental and Safety Specifications

Operating Temperature

10°C to 40°C (50°F to 104°F)

 

Optimal battery performance: 25°C (77°F)

Transit Temperature

-25°C to 55°C (-13°F to 131°F)

Storage Temperature

0°C to 25°C (32°F to 77°F)

 

Recommended battery storage: 59°F (15°C) to 77°F (25°C)

Ventilation

Front air intake, forced air, two fans, positive pressurization,

 

temperature UPS-monitored

Altitude

9,843 ft (3,000m) operating without derating

 

32,810 ft (10,000m) during transportation

Relative Humidity

5–95% noncondensing

Heat Dissipation

5582 BTU/hr maximum online

 

5294 BTU/hr maximum on battery

Audible Noise

<56 dBA at 1 meter distance, typical loads

 

<62 dBA for heavy load, high ambient or high altitude, on battery

Safety Conformance

NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3;

 

EN 55022 Class A (CISPR22 Class A) and IEC 60950; IEC 62040-1-1

Agency Markings

UL, cUL, CE, NOM-NYCE

EMC (Class A)

IEC 62040-2, FCC Part 15, ICES-003, VCCI

Surges

IEEE/ANSI C62.41 Cat B3

 

 

86

Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com