Specifications

Table 21. Battery Specifications

Battery Type

9 Ah sealed, valve-regulated lead acid (VRLA), maintenance-free, minimum 3-year

 

float service life at 77°F (25°C), voltage 192 Vdc (96 cells per string)

Number of Strings

Maximum of 22 strings per full configuration, including UPS batteries (4 EBM-64

 

cabinets or 3 EBM-96 cabinets, plus UPS batteries)

 

UPS-32:

2 strings; UPS-64:

4 strings

 

EBM-64:

4 strings; EBM-96:

6 strings

Battery Replacement

Must be replaced by qualified service technician

Charger

Service configurable 0.5–34A per string, with overall maximum of 34A (limited by

 

input current). Default: 3.4A per string

Charging

Internal battery: approximately 3 hours to 80% usable capacity at nominal line

 

voltage after full load discharge

 

 

 

External battery: no more than 10x discharge time to 90% usable capacity at

 

nominal line voltage after full load discharge

 

Start-on-Battery

Allows start of UPS without utility input

Performance

ABM technology increases battery service life, optimizes recharge time, and

 

provides a warning before the end of useful battery life

Protection

Extended Battery Module output protected by 100A circuit breaker

Table 22. Battery Runtimes (in Minutes) at Full Load

2-High Cabinets

Load

32 Internal UPS

(1) EBM-64

(2) EBM-64

(3) EBM-64

(4) EBM-64

 

Batteries

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 kVA/13.5 kW

4

23

43

65

88

 

 

 

 

 

 

 

 

12 kVA/10.8 kW

6

30

56

85

116

 

 

 

 

 

 

 

 

10 kVA/9 kW

8

37

69

106

144

 

 

 

 

 

 

 

 

8 kVA/7.2 kW

11

49

91

139

189

 

 

 

 

 

 

 

 

 

3-High Cabinets

 

 

 

Load

64 Internal UPS

(1) EBM-96

(2) EBM-96

(3) EBM-96

 

 

Batteries

 

 

 

 

 

 

 

 

15 kVA/13.5 kW

13

43

76

113

 

 

 

 

 

 

 

 

 

12 kVA/10.8 kW

18

56

101

149

 

 

 

 

 

 

 

 

 

10 kVA/9 kW

22

69

124

184

 

 

 

 

 

 

 

 

 

8 kVA/7.2 kW

29

91

164

242

 

 

NOTE Battery times are approximate and vary depending on the load configuration and battery charge.

90

Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com