Communication

Control Terminals

The cables should be connected to the control terminals with cable clips. Input and output terminals have a functional isolation from terminal to terminal. They are connected to the UPS chassis through individual 1 Mresistors.

 

2

+ Polarity

Signal Input 1 (Programmable)

 

1

– Polarity

 

 

 

2

+ Polarity

Signal Input 2 (Programmable)

 

1

– Polarity

UPS

 

 

 

 

Connectors

2

 

 

(see Figure 32

REPO Normally Open

 

1

 

on page 53)

 

 

 

2

REPO Normally Closed

 

 

1

 

 

 

 

 

3

Common

 

 

2

Normally Closed

Relay Output

 

1

Normally Open

 

Figure 39. External Control Terminal Connections

NOTE If using a semiconductor switch type, pay attention to the proper polarity. A relay or other mechanical control is preferred.

Powerware® 9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com

61